46
If a fault is detected during the system test, a corresponding error alert
istriggered,i.e.theerrorindicatoreitherflashes(alarm)orstayson
(error), and a corresponding message appears on the display (also
see chapter 7.1).
After successful conclusion of the system test
, the unit switches to
standby mode
and one of the following displays appears, depending
on the current state of operation:
– TheCondairDualisinstandbymode(nohumidification).
– The Condair Dual humidifies (in addition, the “Humidification on”
indicator lights).
– Drain valve open, the permeate is led directly to the drain conduit
(cause:presetflushingcycleisinprogress(every24hrs.)orthe
conductance of the permeate is too high).
Iftheexternal
safety circuit
(maximumhumidistat,flowcontrol,etc.)is
interrupted,theoppositemessageappearsandthe“Error”and“Humidifi
-
cationon”indicatorslightupintermittently.
If a
fault
is detected during operation, a corresponding error alert is trigger-
ed,i.e.theerrorindicatoreitherflashes(alarm)orstayson(error),anda
corresponding message appears on the display (also see chapter 7.1).
If
maintenance is due
or the
silver ionization electrodes require replace-
ment
, the corresponding message and the current status display appear
intermittently.
– Maintenance due
– Silver ionization electrodes worn
Please consult chapter 6 for further information.
Notes on operation
– Make sure the
minimum working pressure never drops below 2 bar
during operation. In case the working pressure drops below the limit,
check the reverse osmosis system and the fully demineralized water
supply.
– In standby mode the
drain valve is opened for approximately 65 sec-
onds every 24 hours
thusflushingthepermeatesupplyconduit(for
the sake of hygiene).
– Humidificationisnotactivatedifthehumidificationrequestisbelow20%
(2-valveconnectorbox)or15%(3-valveconnectorbox),respectively.