49
Overview of the display level
E
M
perform. [kg/h]
appliance: 100
Condair Dual
ready
perform. [kg/h]
act.value: 33
Demand
25 %
p-pump. int/ext
intern
cond. permeate
7 ‰S
permeate limit
15 ‰S
perform. [kg/h]
valve Y6: 35
perform. [kg/h]
valve Y7: 65
perform. [kg/h]
valve Y8: 0
contr.val.p-punp
95 %
p-pump w.fl.
off
Ag-degermin.
on
act.val Ag curr.
2.4 mA
rem.cap.Ag elec.
7 Ah
elapsed time
180 h
maintenance due
5831 h
controller funct
off
nom. value rF
45 %
P-band
10 %
integr.time
15 min.
perform. limit
100 %
analog signal
0-10 Vdc ( 81%)
error history
07/ 07/ 08/ 10
software version
V6.00
2)
3)
3)
4)
4)
4)
1)
2)
Standard operation
or
Display level
Notes
1) without option Z407 (third spray valve) output indication “0”
2) appears only if internal permeate pump is active (“p-pump. int/ext”/“intern”)
3) appears only if silver ionization is active (“Ag-degermin.” “on”)
4) appears only if internal controller is active (“controller funct” “on”)
next menu option
previous menu option