32
21.
Only the rear rows of ceramic plates require the installation of
anti-drip sheets. However, the anti-drip sheets must be installed
only on the sides of the ceramic plates which overlap with the
plates of a front row (see figure above). The ceramic plates at the
very bottom require the installation of plate sealings instead of
anti-drip sheets.
Insert the anti-drip sheet on the corresponding side between the vertical
section and the overlapping ceramic plate until it comes to a stop. Then,
bend the free end of the anti-drip sheet downwards so that it forms a
curve and touches the lower ceramic plate.
21
Duct, top view
Air flow direction
anti-drip sheet
22. On each side insert the two-part lateral plate sealings. Proceed as fol-
lows: first insert the lower sealing piece between the vertical section
and the ceramic plate, then push it downwards until it comes to a stop.
Now insert the upper sealing piece and align its top end with the upper
edge of the ceramic plate.
Caution: risk of injury!
To prevent injury resulting from the rough
ceramic plates or the lateral plate sealings use a spattle (or a similar
tool) to insert the plate sealings.
23. Finally, push the two upper plate sealings down until they come to a
stop.
23
22