Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
78
FieldSmart
®
Fiber Active Cabinet (FAC) 900
Installation Manual
_________________________________________________________
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
To install the cabinet or EXM ground connection
Open the side cabinet or EXM door.
Route the earth ground wire to the main ground bar (or subground bar for the EXM) and cut the wire to length.
Using a ratcheting crimp tool with embossing dies, attach a two-hole compression lug (#2–6 AWG, 3/4-inch
hole spacing) to the earth ground wire. Ensure that the correct lug is used to match the earth ground wire.
At the middle of the ground bar, locate a ground position with 3/4-inch stud spacing. Remove the nuts from the
identified terminal studs.
Attach the earth ground wire's two-hole lug onto the 3/4-inch ground terminal studs (labeled
Earth Ground
) per
PANI guidelines.
Re-connect the nuts to the ground terminal studs and tighten to 26 inch-lbs. of torque.