109
FieldSmart
®
Fiber Active Cabinet (FAC) 900
__________________________________________________________
Installation Manual
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeClearfield.com • [email protected]
Manual 020420 REV B - April 2019
e.
In the Temperature Compensation section, enter the upper/lower temperature breakpoint temperature and
voltage in the respective boxes.
Battery Type
Upper Temperature
Breakpoint
Lower Temperature
Breakpoint
Temperature in
C (in F)
Voltage
Temperature in
C (in F)
Voltage
Northstar NSB60FT Red
50 (122)
53.28
10 (50)
55.2
Enersys SBS B14
50 (122)
52.08
10 (50)
55.92
Northstar NSB100FT Red
50 (122)
53.28
10 (50)
55.2
Northstar NSB170FT Red
50 (122)
53.28
10 (50)
55.2
Enersys SBS 190F
50 (122)
52.08
10 (50)
55.92