Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
124
FieldSmart
®
Fiber Active Cabinet (FAC) 900
Installation Manual
_________________________________________________________
Step 6:
Step 7:
Step 8:
Step 9:
Connect the heater power and ground wires as follows:
a.
Route the ground and power wires from the rear of the battery enclosure to the mounting bracket installed in
step 3.
b.
Attach the ground wire to the mounting stud located on the bracket using the supplied Keps nuts and star
washers.
c.
Snap the power cord face-up into it's cutout in the mounting bracket installed in step 3.
(AC load center) Install the battery heater jumper cable as follows:
a.
Snap the jumper cable's power connector face down into it's cutout in the mounting bracket installed in step 3.
b.
Route the jumper cable to the rear of the AC load center and feed it through the cord grip in the AC input hole.
c.
Attach the supplied fast-on lug to the stripped end of the black wire, and then connect the terminated black
wire to the load terminal of the 5A Battery Heater breaker.
d.
Connect the white lead to the Batt Htr position on the panel board Neutral bar.
Note:
An AC wiring label is attached behind the load center front panel for reference.
e.
Tighten the cord grip around the jumper cable at the rear of the load center.
(AC junction box) Install the battery heater jumper cable as follows:
a.
Snap the jumper cable's power connector face down into it's cutout in the mounting bracket installed in step 3.
b.
Route the jumper cable to the rear of the AC junction box and feed it through.
c.
Connect the L1 (black) and N (white) leads to the (Optional) Battery Heater terminal block position.
Note:
An AC wiring label is attached behind the junction box front panel for reference.
d.
Tighten the cord grip around the jumper cable at the rear of the junction box.
After the batteries are installed, apply power as follows:
Note:
For battery installation instructions, see Installing Batteries.
a.
At the AC load center, switch
ON
the 5A Battery Heater breaker, or
b.
Switch on the 5A Battery Heater breaker at the external power source that feeds the AC junction box.