To install a generator connector into an FAC 900 cabinet
Unpack the generator connector from its shipping packaging.
Attach the generator connector to the cabinet mounting fixture as follows:
a.
From the exterior side of the cabinet, feed the generator connector wires into the cabinet through the mount-
ing fixture opening.
b.
Insert the generator connector into the mounting fixture, aligning the mounting holes with the counterpart
holes in the fixture.
c.
Install the (4) tamper-resistant screws removed previously to attach the generator connector.
Connect the generator connector wires to the AC load center as follows:
a.
Route the generator connector wires through the access hole in the right side of the AC load center.
b.
Terminate the generator connector wires to the load center as follows:
• Connect the green wire to the ground bar.
• Connect the white wire to the neutral bar.
• Connect the black and red wires to the Gen. Conn. breaker.
Note:
Refer to the AC load center wiring diagram (on Clearfield’s website, seeclearfield.com) for guidance. An
AC wiring label is attached behind the load center front panel for reference.
Replace the AC load center cover panel.
Install the Gen Conn ID label on the cover panel directly under the Gen Conn 30 Amp breaker.
At the AC load center, switch all breakers to
ON
.
At the local power transfer switch, restore AC power to the cabinet.