D-13
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Appendix D Chassis and Module Power and Heat Values
Table D-12
lists the power and the heat numbers for the 10BASE Ethernet switching modules.
Table D-13
lists the power and the heat numbers for the FlexWAN and the enhanced FlexWAN modules.
Table D-14
lists the power and the heat numbers for the available service modules.
Table D-12
Power Requirements and Heat Dissipation—10BASE Ethernet Switching Modules
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
WS-X6024-10FL-MT
24-port 10BASE-FL Ethernet
module
1.52
63.84
79.8
272.52
85.81
293.0
Table D-13
Power Requirements and Heat Dissipation—FlexWAN and Enhanced FlexWAN Modules
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
WS-X6182-2PA
FlexWAN module
2.38
99.96
125
426.7
134.35
458.82
WS-X6582-2PA
Enhance FlexWAN module
2.50
105.00
131.25
448.22
141.13
481.96
Table D-14
Power Requirements and Heat Dissipation—Service Modules
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
ACE10-6500-K9
Applications Control Engine
(ACE) module
5.23
219.66
274.58
937.67
295.24
1008.25
WS-SVC-ADM-1-K9
Traffic Anomaly Detector
Module
4.00
168.00
210.00
717.15
225.81
771.13
WS-SVC-AGM-1-K9
Anomaly Guard Module
4.00
168.00
210.00
717.15
225.81
771.13
WS-SVC-AON-1-K9
Application-Oriented
Networking (AON) module
4.00
168.00
210.00
717.15
225.81
771.31
WS-SVC-CMM
Communications Media Module
6.00
252.0
315.0
1075.73
338.71
1156.69