A-43
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Appendix A Power Supply Specifications
4000 W AC-Input and DC-Input Power Supplies
Table A-29
list the specification for the 4000 W DC-input power supply.
Branch circuit requirement
Each chassis power supply should have its own dedicated, fused-branch
circuit:
•
For North America—30 A
•
For International—Circuits should be sized according to local and
national codes
•
All AC power supply inputs are fully isolated.
–
Source AC can be out of phase between multiple power supplies
in the same chassis, which means that PS1 can be operating
from phase A and PS2 can be operating from phase B.
–
For high-line operation, the power supply operates with the hot
conductor wired to a source AC phase and the neutral conductor
wired either to ground or to another source AC phase as long as
the net input voltage is in the range of 170 to 264 VAC.
–
Source AC can be out of phase between AC inputs on power
supplies that are equipped with multiple AC inputs, which
means that power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.
Output capacity
4000 W maximum
Power supply output
•
15 A @ +3.3 VDC
•
5 A @ +5 VDC
•
10 A @ +12 VDC
•
90.36 A @ +42 VDC
Output holdup time
20 ms minimum
kVA rating
1
5.4 kVA maximum
Heat dissipation
17,065 BTU/hour (approx.)
Weight
22.2 lb (10.1 kg)
1.
The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard
circuits and transformers to power a switch.
Table A-28
4000 W AC-Input Power Supply Specifications (continued)
Specification
Description