4-8
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 4 Removal and Replacement Procedures
Removing and Installing the AC-Input Power Supplies
Figure 4-5
Handling a 2700 W AC-Input Power Supply
Step 6
If the power supply bay is to remain empty, install a blank power supply filler plate (Cisco
part number 800-16727-01) over the opening and secure it with the captive installation screws.
Installing a 2700 W AC-Input Power Supply
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
Statement 1045
To install an AC-input power supply, follow these steps:
Step 1
Ensure that the system (earth) ground connection has been made. For ground connection instructions,
see the
“Establishing the System Ground” section on page 3-52
.
Step 2
If necessary, remove the blank power supply filler plate from the chassis power supply bay opening by
loosening the captive installation screws.
Step 3
Verify that the power switch on the power supply is in the off (0) position.
Step 4
Grasp both power supply handles. (See
Figure 4-5
.) Slide the power supply into the power supply bay.
Make sure that the power supply is fully seated in the bay.
Step 5
Securely tighten the power supply captive installation screws.
Warning
Power supply captive installation screws must be tight to ensure protective grounding continuity.
Statement 289
185081
PWR-2700-AC/4
ALL FASTENERS MUST BE FULLY ENG
AGED
PRIOR TO OPERATING THE
POWER SUPPLY
ALL FASTENERS MUST BE FULLY ENGAGED
PRIOR TO OPERATING THE POWER SUPPLY
PWR-2700-AC/4
Power Supply 2
(redundant)
Power Supply 1