91
<2 Step Feeding, 2 Step Discharging Mode_2>
Relay Operation Graph upon Setting (F6.03-9)
1. Required set value input : Step 2(SP2) – Supply Fall(SP8) > Step 1(SP1),
Step 4(SP4) – Discharge Fall(SP9) > Step 3(SP3)
2.
SP1:
Step 1,
SP2:
Step 2,
SP3:
Step 3,
SP4:
Step 4,
SP5:
Upper Limit NG,
SP6:
Lowest Limit NG,
SP7:
Final,
SP8:
Supply Fall,
SP9:
Discharge Fall
3. Near zero output is according to the specified range in F1-23
4. T1 : Refer to F6.04 (Delay time of weighing Finish relay output)
T2 : Refer to F6.05 (Operation time of weighing Finish relay output)
5. Relay Output
Step 1 : ON when ( SP1 – SP8 ≤
Weight
)
Step 2 : ON when ( SP2 ≤
Weight
)
Step 3 : ON when ( SP3 ≤
Discharge
Weight
)
Step 4 : ON when ( SP4 – SP9 ≤
Discharge
Weight
)
Finish : On after T1 (set time), ON during T2 (set time)
Near Zero : F1-23 set value ≥
Weight
≥ 0 range output
6. Status lamp in the front panel is operated in the same manner as the RELAY output.
Summary of Contents for CI-400 Series
Page 1: ... 2 ...
Page 10: ...11 2 Specifications in Appearance 2 1 External Dimension ...
Page 29: ... 30 4 2 How to Seal the Indicator Sealing ...
Page 93: ... 94 Connection of Input Output Input AContact Output AContact ...
Page 117: ... 118 MEMO ...
Page 118: ...119 MEMO ...
Page 119: ... 120 MEMO ...
Page 120: ...121 ...