84
<Loss in weight_3 Step Discharging Mode >
Relay Operation Graph upon Setting (F6.03-2)
1. Required set value input : Final (SP7) > Step 1(SP1) > Step 2(SP2) > Fall (SP3)
2.
SP1:
Step1,
SP2:
Step2,
SP3:
Fall,
SP5:
Upper Limit NG,
SP6:
Lowest Limit NG,
SP7:
Final
3. Near zero output is according to the specified range in F1-23
4. Relay Output
Step 1 : ON OFF when (SP7 – SP1 ≤
Discharge Weight
)
Step 2 : ON OFF when (SP7 – SP2 ≤
Discharge
Weight
)
Step 3 : ON OFF when (SP7 – SP3 ≤
Discharge
Weight
)
Lowest Limit NG : ON when {
Discharge
Weight
< (SP7 – SP6)}
Upper Limit NG : ON when {(SP7 + SP5) <
Discharge
Weight }
Near Zero : F1-23 set value ≥
Weight
≥ 0 range output
5. Status lamp in the front panel is operated in the same manner as the RELAY output.
.