<2 Step Feeding, 1 Step Discharging Mode>
Relay Operation Graph upon Setting (F6.03-5)
1. Required set value input : Step 2(SP2) > Step 1(SP1) > Final (SP7) > Fall (SP3)
2.
SP1:
Step1,
SP2:
Step2,
SP3:
Fall,
SP5:
Upper Limit NG,
SP6:
Lowest Limit NG,
SP7
: Final
3. Near zero output is according to the specified range in F1-23
4. T1 : Refer to F6.04 (Delay time of weighing Finish relay output)
T2 : Refer to F6.05 (Operation time of weighing Finish relay output)
T5 : Refer to F6.09 (Operation(ON) time of weighing NG relay output)
5. Relay Output
Step 1 : ON when ( SP1 ≤
Weight
), OFF When start input
Step 2 : ON when ( SP2 ≤
Weight
), OFF When start input
Step 3 : ON When start input
,
OFF when {(SP7 – SP3) ≤
Discharge
Weight},
Finish : On after T1 (set time), ON during T2 (set time)
Error : When weighing is completed {
Discharge
Weight
< (SP7 – SP6)} or
{(SP7 + SP5) <
Discharge
Weight},
ON for the during of T5 (set time)
Near Zero : F1-23 set value ≥
Weight
≥ 0 range output
6. Status lamp in the front panel is operated in the same manner as the RELAY output.