85
<1 Step Feeding, 2 Step Discharging Mode_1>
Relay Operation Graph upon Setting (F6.03-3)
1. Required set value input : Step 1(SP1) > Final(SP7) > Step 2(SP2) > Fall(SP3)
2.
SP1:
Step1,
SP2:
Step2,
SP3:
Fall,
SP5:
Upper Limit NG,
SP6:
Lowest Limit NG,
SP7:
Final
3. Near zero output is according to the specified range in F1-23
4. T1 : Refer to F6.04 (Delay time of weighing Finish relay output)
5. Relay Output
Step 1 : ON when ( SP1 ≤
Weight
)
Step 2 : ON when {(SP7 – SP2) ≤
Discharge
Weight},
OFF after T1 (set time),
Step 3 : ON when {(SP7 – SP3) ≤
Discharge
Weight},
OFF after T1 (set time),
Lowest Limit NG : ON when {
Discharge
Weight
< (SP7 – SP6)}
Upper Limit NG : ON when {(SP7 + SP5) <
Discharge
Weight }
Near Zero : F1-23 set value ≥
Weight
≥ 0 range output
6. Status lamp in the front panel is operated in the same manner as the RELAY output.
Summary of Contents for CI-400 Series
Page 1: ... 2 ...
Page 10: ...11 2 Specifications in Appearance 2 1 External Dimension ...
Page 29: ... 30 4 2 How to Seal the Indicator Sealing ...
Page 93: ... 94 Connection of Input Output Input AContact Output AContact ...
Page 117: ... 118 MEMO ...
Page 118: ...119 MEMO ...
Page 119: ... 120 MEMO ...
Page 120: ...121 ...