187
SG.CF
LAT.L
LAT Limit Config
0 to 20
^F
HTLATLIM
10
60, 63, 64, 67
SG.CF
LIM.M
Limit Switch Monitoring?
Yes/No
HTLIMMON
Yes
60, 63, 64, 65, 67
SG.CF
SW.H.T
Limit Switch High Temp
80 to 210
dF
HT_LIMHI
170
60, 63, 64, 65, 67
SG.CF
SW.L.T
Limit Switch Low Temp
80 to 210
dF
HT_LIMLO
160
60, 63, 64, 65, 67
SG.CF
HT.P
Heat Control Prop. Gain
0 to 1.5
HT_PGAIN
1
60, 63, 64
SG.CF
HT.D
Heat Control Derv. Gain
0 to 1.5
HT_DGAIN
1
60, 63, 64
SG.CF
HT.TM
Heat PID Rate Config
30 to 300
sec
HTSGPIDR
90
60, 63, 64
HH.CF
HYDRONIC HEAT CONFIGS
HH.CF
HW.P
Hydronic Ctl.Prop. Gain
0 to 1.5
HW_PGAIN
1
60, 62, 63
HH.CF
HW.I
Hydronic Ctl.Integ. Gain
0 to 1.5
HW_IGAIN
1
60, 62, 63
HH.CF
HW.D
Hydronic Ctl.Derv. Gain
0 to 1.5
HW_DGAIN
1
60, 62, 63
HH.CF
HW.TM
Hydronic PID Rate Config
15 to 300
sec
HOTWPIDR
90
60, 62, 63
HH.CF
ACT.C
HYDR.HEAT ACTUATOR CFGS.
HH.CF
ACTC
SN.1
Hydronic Ht.Serial Num.1
0 to 9999
HTCL_SN1
0
60, 62, 63
HH.CF
ACTC
SN.2
Hydronic Ht.Serial Num.2
0 to 6
HTCL_SN2
0
60, 62, 63
HH.CF
ACTC
SN.3
Hydronic Ht.Serial Num.3
0 to 9999
HTCL_SN3
0
60, 62, 63
HH.CF
ACTC
SN.4
Hydronic Ht.Serial Num.4
0 to 254
HTCL_SN4
0
60, 62, 63
HH.CF
ACTC
C.A.LM
Hydr.Ht.Ctl.Ang.Lo Limit
0-90
HTCLCALM
85
60, 62
SP
SUPPLY STATIC PRESS.CFG.
SP.CF
Static Pressure Config
Enable/Disable
STATICFG
Disable
39, 69, 70, 72
SP.SV
Staged Air Volume Control
Enable/Disable
STGAVCFG
Disable
69, 70
SP.S
Static Pressure Sensor
Enable/Disable
SPSENS
Disable
69, 70
SP.LO
Static Press. Low Range
-10 to 0
in. W.C. SP_LOW
0
70
SP.HI
Static Press. High Range
0 to 10
in. W.C. SP_HIGH
5
70
SP.SP
Static Pressure Setpoint
0 to 5
in. W.C. SPSP
1.5
33, 69, 70, 71
SP.MN
VFD Minimum Speed
0 to 100
%
STATPMIN
20
39, 70
SP.MX
VFD Maximum Speed
0 to 100
%
STATPMAX
100
39, 70
SP.FS
VFD Fire Speed Over.
0 to 100
%
STATPFSO
100
70, 84
SP.RS
Stat. Pres. Reset Config
0 to 4 (multi-text strings)
SPRSTCFG
0
39, 45, 70, 71, 72
SP.RT
SP Reset Ratio
0.00 to 2.00
SPRRATIO
0.20
70
SP.LM
SP Reset Limit
0.00 to 2.00
SPRLIMIT
0.75
70, 71
SP.EC
SP Reset Econo. Position
0 to 100
%
ECONOSPR 5
70, 71
S.PID
STAT.PRESS.PID CONFIGS
S.PID
SP.TM
Stat.Pres.PID Run Rate
5 to 120
sec
SPIDRATE
15
70, 71
S.PID
SP.P
Static Press. Prop. Gain
0 to 5
STATP_PG
0.5
70, 71
S.PID
SP.I
Static Pressure Intg. Gain
0 to 2
STATP_IG
0.5
70, 71
S.PID
SP.D
Static Pressure Derv. Gain
0 to 5
STATP_DG
0.3
70, 71
ECON
ECONOMIZER CONFIGURATION
EC.EN
Economizer Installed?
Yes/No
ECON_ENA
Yes
34, 75, 76
EC2.E
Econ.Act.2 Installed?
Yes/No
ECON_TWO No
34, 75, 76
EC.MN
Economizer Min.Position
0 to 100
%
ECONOMIN
5
34, 75, 76, 79, 125
EC.MX
Economizer Max.Position
0 to 100
%
ECONOMAX 98
34, 56, 75, 76
E.TRM
Economzr Trim For SumZ ?
Yes/No
ECONTRIM
Yes
34, 54, 75, 76
E.SEL
Econ ChangeOver Select
0 to 3 (multi-text strings)
ECON_SEL
0
34, 41, 73, 74, 76, 77
DDB.C
Diff Dry Bulb RAT Offset
0 to 3
dF
EC_DDBCO
0
74, 76
OA.E.C
OA Enthalpy ChgOvr Selct
1 to 5 (multi-text strings)
OAEC_SEL
4
34, 76, 77
OA.EN
Outdr.Enth Compare Value
18 to 28
OAEN_CFG
24
34, 76, 77
OAT.L
High OAT Lockout Temp
-40 to 120
dF
OAT_LOCK
60
34, 76, 77
O.DEW
OA Dewpoint Temp Limit
50 to 62
dF
OADEWCFG 55
34, 76, 78
ORH.S
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
34, 45, 76, 77, 95
CFM.C
OUTDOOR AIR CFM CONTROL
CFM.C
OCF.S
Outdoor Air CFM Sensor
Enable/Disable
OCFMSENS Disable
34, 45, 73, 76, 79, 87
CFM.C
O.C.MX
Economizer Min.Flow
0 to 20000
CFM
OACFMMAX 2000
34, 76, 79, 87
CFM.C
O.C.MN
IAQ Demand Vent Min.Flow
0 to 20000
CFM
OACFMMIN
0
34, 76, 79, 87
CFM.C
O.C.DB
Econ.Min.Flow Deadband
200 to 1000
CFM
OACFM_DB
400
34, 76, 79, 87
E.CFG
ECON.OPERATION CONFIGS
E.CFG
E.P.GN
Economizer Prop.Gain
0.7 to 3.0
EC_PGAIN
1
76
E.CFG
E.RNG
Economizer Range Adjust
0.5 to 5
^F
EC_RANGE
2.5
76
E.CFG
E.SPD
Economizer Speed Adjust
0.1 to 10
EC_SPEED
0.75
76
E.CFG
E.DBD
Economizer Deadband
0.1 to 2
^F
EC_DBAND
0.5
76
UEFC
UNOCC.ECON.FREE COOLING
UEFC
FC.CF
Unoc Econ Free Cool Cfg
0-2 (multi-text strings)
UEFC_CFG
0
76, 78
UEFC
FC.TM
Unoc Econ Free Cool Time
0 to 720
min
UEFCTIME
120
76, 78
UEFC
FC.L.O
Un.Ec.Free Cool OAT Lock
40 to 71
dF
UEFCNTLO
50
76
ACT.C
ECON.ACTUATOR CONFIGS
ACTC
SN.1.1
Econ Serial Number 1
0 to 9999
ECON_SN1
0
76
ACTC
SN.1.2
Econ Serial Number 2
0 to 6
ECON_SN2
0
76
ACTC
SN.1.3
Econ Serial Number 3
0 to 9999
ECON_SN3
0
76
ACTC
SN.1.4
Econ Serial Number 4
0 to 254
ECON_SN4
0
76
ACTC
C.A.L1
Econ Ctrl Angle Lo Limit
0 to 90
ECONCALM
85
76, 78
ACTC
SN.2.1
Econ 2 Serial Number 1
0 to 9999
ECN2_SN1
0
76
ACTC
SN.2.2
Econ 2 Serial Number 2
0 to 6
ECN2_SN2
0
76
ACTC
SN.2.3
Econ 2 Serial Number 3
0 to 9999
ECN2_SN3
0
76
ACTC
SN.2.4
Econ 2 Serial Number 4
0 to 254
ECN2_SN4
0
76
APPENDIX A — LOCAL DISPLAY TABLES
Table H — MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...