201
DLVT (cont)
Dmd Level(-) Lo Cool Off
0.5 to 2.0
^F
DMDLCOFF
1
Cool Trend Demand Level
0.1 to 5.0
^F
CTRENDLV
0.1
Heat Trend Demand Level
0.1 to 5.0
^F
HTRENDLV
0.1
Cool Trend Time
30 to 600
sec
CTRENDTM
120
Heat Trend Time
30 to 600
sec
HTRENDTM
120
DMDL
Demand Limit Select
0 to 3
DMD_CTRL
0
Demand Limit at 20 ma
0 to 100
%
DMT20MA
100
Loadshed Group Number
0 to 99
SHED_NUM
0
Loadshed Demand Delta
0 to 60
%
SHED_DEL
0
Maximum Loadshed Time
0 to 120
min
SHED_TIM
60
Demand Limit Sw.1 Setpt.
0 to 100
%
DLSWSP1
80
Demand Limit Sw.2 Setpt.
0 to 100
%
DLSWSP2
50
ECON
Economizer Installed ?
Yes/No
ECON_ENA
Yes
Econ. Act.2 Installed ?
Yes/No
ECON_TWO
No
Economizer Min.Position
0 to 100
%
ECONOMIN
5
Economizer Max.Position
0 to 100
%
ECONOMAX
98
Economzr trim for sumZ ?
Yes/No
ECONTRIM
Yes
Econ ChangeOver Select
0 to 3
ECON_SEL
0
OA Enthalpy ChgOvr Selct
1 to 5
OAEC_SEL
4
Outdr.Enth Compare Value
18 to 28
BTU/LBM
OAEN_CFG
24
High OAT Lockout Temp
55 to 120
dF
OAT_LOCK
60
OA Dewpoint Temp Limit
50 to 62
dF
OADEWCFG
55
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
Outdoor Air CFM Sensor
Enable/Dsable
OCFMSENS
Dsable
Economizer Min.Flow
0 to 20000
CFM
OACFMMAX
2000
IAQ Demand Vent Min.Flow
0 to 20000
CFM
OACFMMIN
0
Econ.Min.Flow Deadband
200 to 1000
CFM
OACFM_DB
400
Economizer Prop.Gain
0.7 to 3.0
EC_PGAIN
1
Economizer Range Adjust
0.5 to 5
^F
EC_RANGE
2.5
Economizer Speed Adjust
0.1 to 10
EC_SPEED
0.75
Economizer Deadband
0.1 to 2
^F
EC_DBAND
0.5
Unoc Econ Free Cool Cfg
0-2
UEFC_CFG
0
Unoc Econ Free Cool Time
0-720
min
UEFCTIME
120
Un.Ec.Free Cool OAT Lock
40-70
dF
UEFCNTLO
50
Econ Serial Number 1
0-9999
ECON_SN1
Econ Serial Number 2
0-6
ECON_SN2
Econ Serial Number 3
0-9999
ECON_SN3
Econ Serial Number 4
0-254
ECON_SN4
Econ Ctrl Angle Lo Limit
0-90
ECONCALM
85
Econ 2 Serial Number 1
0-9999
ECN2_SN1
Econ 2 Serial Number 2
0-6
ECN2_SN2
Econ 2 Serial Number 3
0-9999
ECN2_SN3
Econ 2 Serial Number 4
0-254
ECN2_SN4
Ecn2 Ctrl Angle Lo Limit
0-90
ECN2CALM
85
EDTR
EDT Reset Configuration
0 to 3
EDRSTCFG
2
Reset Ratio
0 to 10
RTIO
3
Reset Limit
0 to 20
^F
LIMT
10
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
HEAT
Heating Control Type
0 to 5
HEATTYPE
0
Heating Supply Air Setpt
80-120
dF
SASPHEAT
85
Occupied Heating Enabled
Yes/No
HTOCCENA
No
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
Staged Heat Type
0 to 8
HTSTGTYP
0
Max Cap Change per Cycle
5 to 45
HTCAPMAX
45
St.Ht DB min.dF/PID Rate
0 to 5
HT_MR_DB
0.5
St.Heat Temp. Dead Band
0 to 5
^F
HT_SG_DB
2
APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
DEFAULT
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...