Table 26 — Supply Fan Motor Limitations (Sizes 030-070)
LEGEND
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with Energy Policy Act (EPACT) Standards
effective October 24, 1997.
Table 27 — Supply Fan Motor Limitations (Sizes 075-100)
LEGEND
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with Energy Policy Act (EPACT) Standards
effective October 24, 1997.
Table 28 — Optional High-Capacity Power Exhaust Systems Motor Limitations (Sizes 075-100)
LEGEND
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with Energy Policy Act (EPACT) Standards
effective October 24, 1997.
HIGH-EFFICIENCY MOTORS
Nominal
Maximum
Maximum Amps
Rated
Efficiency
Bhp
BkW
Bhp
BkW
230 v
380 v
460 v
575 v
7.5
5.60
8.7
6.49
22.0
—
—
—
84.1
9.5
7.09
—
15.0
12.0
10.0
88.5
10
7.46
10.2
7.61
28.0
—
—
—
89.5
11.8
8.80
—
20.7
14.6
12.0
89.5
15
11.19
15.3
11.41
43.8
—
—
—
91.0
18.0
13.43
—
27.0
21.9
19.0
91.0
20
14.92
22.4
16.71
62.0
—
—
—
91.0
23.4
17.46
—
37.4
28.7
23.0
91.0
25
18.65
28.9
21.56
72.0
—
—
—
91.7
29.4
21.93
—
43.8
37.4
31.0
91.7
30
22.38
35.6
26.56
95.0
—
—
—
92.4
34.7
25.89
—
—
48.0
36.3
92.4
40
29.80
42.0
31.30
—
—
55.0
—
93.0
PREMIUM-EFFICIENCY MOTORS
Nominal
Maximum
Maximum Amps
Rated
Efficiency
Bhp
BkW
Bhp
BkW
230 v
460 v
7.5
5.60
8.7
6.49
22.0
—
91.7
9.5
7.09
—
12.0
91.7
10
7.46
10.2
7.61
28.0
—
91.7
11.8
8.80
—
15.0
91.7
15
11.19
15.3
11.41
43.8
—
93.0
18.0
13.43
21.9
93.0
20
14.92
22.4
16.71
58.2
—
93.6
23.4
17.46
—
28.7
93.6
25
18.65
28.9
21.56
73.0
—
93.6
29.4
21.93
—
36.3
93.6
30
22.38
35.6
26.56
82.6
—
93.6
34.7
25.89
—
41.7
93.6
40
29.84
42.0
31.33
—
55.0
94.5
Bhp
—
Brake Horsepower
BkW —
Brake Kilowatts
HIGH-EFFICIENCY MOTORS
Nominal
HP
BkW
Max Bhp
Max BkW
Max Amps
Rated
Efficiency
460 V 575 V
30
22.4
34.7
25.9
48.0
36.3
92.4
40
29.8
42.0
31.3
55.0
48.8
93.0
50
37.3
57.5
42.9
71.0
52.8
93.0
60
44.8
69.0
51.5
82.6
60.5
93.6
75
59.5
86.25
64.3
99.5
N/A
94.1
PREMIUM-EFFICIENCY MOTORS
Nominal
HP
BkW
Max Bhp
Max BkW
Max Amps
Rated
Efficiency
460 V 575 V
30
22.4
34.7
25.9
41.7
N/A
93.6
40
29.8
42.0
31.3
55.0
N/A
94.5
50
37.3
57.5
42.9
71.0
N/A
94.5
60
44.8
69.0
51.5
75.0
N/A
95.4
75
59.5
86.25
64.3
95.5
N/A
95.4
Bhp —
Brake Horsepower
BkW —
Brake Kilowatts
N/A
—
Not Available
HIGH-EFFICIENCY MOTORS
Nominal
HP
BkW
Max Bhp
Max BkW
Max Amps (ea)
Rated
Efficiency
460 V
575 V
20
14.9
23.6
17.6
14.6
12.0
89.5
30
22.4
36.0
26.9
21.9
19.0
91.0
40
29.8
46.8
34.9
28.7
23.0
91.0
50
37.3
58.8
43.9
37.4
31.0
91.7
60
44.8
69.0
51.5
48.0
36.3
92.4
PREMIUM-EFFICIENCY MOTORS
Nominal
HP
BkW
Max Bhp
Max BkW
Max Amps (ea)
Rated
Efficiency
460 V
575 V
20
14.9
23.6
17.6
15.0
N/A
91.7
30
22.4
36.0
26.9
21.9
N/A
93.0
40
29.8
46.8
34.9
28.7
N/A
93.6
50
37.3
58.8
43.9
36.3
N/A
93.6
60
44.8
69.0
51.5
41.7
N/A
93.6
Bhp —
Brake Horsepower
BkW —
Brake Kilowatts
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...