22
Table 16 — Fan Performance — 50P2,P3070 Units with Discharge Plenum and 50P4,P5070 Units
LEGEND
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Perfor-
mance tables.
3. Conversion — Bhp to kW:
See Physical Data table for motor efficiency.
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
14,000
268
2.64
304
3.32
335
4.02
364
4.76
391
5.55
418
6.39
444
7.27
468
8.20
17,500
316
4.67
348
5.54
376
6.39
402
7.25
426
8.14
449
9.06
472
10.03
493
11.03
21,000
366
7.61
395
8.66
421
9.69
444
10.71
466
11.73
487
12.78
507
13.85
527
14.94
24,500
417
11.61
444
12.87
467
14.09
489
15.28
509
16.47
529
17.66
547
18.86
565
20.08
28,000
470
16.88
493
18.35
515
19.77
536
21.15
555
22.51
573
23.87
590
25.22
607
26.59
30,000
500
20.52
522
22.11
543
23.64
563
25.14
581
26.61
599
28.06
616
29.52
632
30.97
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
14,000
493
9.17
516
10.19
539
11.24
562
12.33
583
13.45
605
14.60
625
15.77
645
16.96
17,500
515
12.07
535
13.14
556
14.26
576
15.42
595
16.61
615
17.84
634
19.09
652
20.39
21,000
546
16.07
564
17.23
583
18.42
600
19.64
618
20.90
635
22.19
653
23.51
669
24.86
24,500
583
21.32
600
22.59
616
23.87
633
25.18
649
26.53
664
27.89
680
29.29
695
30.71
28,000
623
27.96
639
29.35
655
30.75
670
32.18
685
33.63
699
35.09
—
—
—
—
30,000
648
32.43
663
33.90
678
35.38
—
—
—
—
—
—
—
—
—
—
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.4
3.6
3.8
4.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
14,000
665
18.18
684
19.42
703
20.68
721
21.95
17,500
671
21.70
689
23.05
706
24.42
724
25.82
21,000
686
26.24
703
27.67
719
29.11
735
30.59
24,500
711
32.17
726
33.65
741
35.16
—
—
28,000
—
—
—
—
—
—
—
—
30,000
—
—
—
—
—
—
—
—
50P3,P5 units only.
Bhp —
Brake Horsepower
Kilowatts =
Bhp x 0.746
Motor efficiency
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...