Table 9 — Fan Performance — 48P2,P3,P4,P5070 and 50P2,P3070 Units without Discharge Plenum*
LEGEND
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Perfor-
mance tables.
3. Conversion — Bhp to kW:
See Physical Data table for motor efficiency.
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
14,000
258
2.23
297
2.80
330
3.38
362
4.02
392
4.73
422
5.53
451
6.42
480
7.37
17,500
302
3.92
338
4.67
368
5.39
395
6.10
421
6.84
446
7.64
471
8.50
495
9.42
21,000
348
6.36
380
7.29
408
8.18
434
9.04
457
9.88
479
10.74
501
11.64
522
12.57
24,500
397
9.74
424
10.80
450
11.88
475
12.91
497
13.91
517
14.89
537
15.88
556
16.89
28,000
447
14.18
470
15.35
494
16.60
516
17.82
538
19.01
558
20.16
576
21.29
594
22.41
30,000
476
17.29
497
18.50
519
19.82
541
21.15
562
22.45
581
23.70
599
24.93
617
26.14
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
14,000
507
8.39
533
9.46
558
10.57
582
11.71
605
12.89
627
14.08
648
15.29
668
16.52
17,500
519
10.42
542
11.48
565
12.60
588
13.78
610
15.02
632
16.30
653
17.62
674
18.99
21,000
543
13.56
563
14.60
583
15.69
603
16.84
623
18.05
643
19.31
662
20.63
682
21.99
24,500
575
17.93
593
18.99
611
20.10
629
21.24
646
22.43
664
23.67
681
24.96
698
26.29
28,000
612
23.55
628
24.69
645
25.86
661
27.05
677
28.27
692
29.53
708
30.82
723
32.15
30,000
634
27.34
650
28.56
666
29.78
681
31.02
696
32.28
711
33.56
726
34.88
—
—
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.4
3.6
3.8
4.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
14,000
687
17.76
706
19.01
724
20.27
741
21.54
17,500
694
20.38
713
21.79
732
23.24
—
—
21,000
701
23.41
719
24.87
738
26.38
—
—
24,500
715
27.67
732
29.10
749
30.58
—
—
28,000
739
33.51
—
—
—
—
—
—
30,000
—
—
—
—
—
—
—
—
48/50P3,P5 units only.
Bhp —
Brake Horsepower
Kilowatts =
Bhp x 0.746
Motor efficiency
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...