183
APPENDIX A — LOCAL DISPLAY TABLES
Table C — MODE — TEMPERATURES
Table D — MODE — PRESSURES
Table E — MODE — SETPOINTS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
AIR.T
AIR TEMPERATURES
CTRL
CONTROL TEMPS
CTRL
EDT
Evaporator Discharge Tmp
dF
EDT
CTRL
LAT
Leaving Air Temperature
dF
LAT
CTRL
MAT
Mixed Air Temperature
dF
MAT
CTRL
R.TMP
Controlling Return Temp
dF
RETURN_T
forcible
CTRL
S.TMP
Controlling Space Temp
dF
SPACE_T
forcible
SAT
Air Tmp Lvg Supply Fan
dF
SAT
OAT
Outside Air Temperature
-40 to 240
dF
OAT
forcible
RAT
Return Air Temperature
dF
RAT
forcible
SPT
Space Temperature
-40 to 240
dF
SPT
forcible
SPTO
Space Temperature Offset
^F
SPTO
forcible
CCT
Air Temp Lvg Evap Coil
dF
CCT
S.G.LS
Staged Heat LAT Sum
dF
LAT_SGAS
S.G.L1
Staged Heat LAT 1
dF
LAT1SGAS
S.G.L2
Staged Heat LAT 2
dF
LAT2SGAS
S.G.L3
Staged Heat LAT 3
dF
LAT3SGAS
S.G.LM
Staged Gas Limit Sw.Temp
dF
LIMSWTMP
REF.T
REFRIGERANT TEMPERATURES
SCT.A
Cir A Sat.Condensing Tmp
dF
SCTA
SST.A
Cir A Sat.Suction Temp.
dF
SSTA
SCT.B
Cir B Sat.Condensing Tmp
dF
SCTB
SST.B
Cir B Sat.Suction Temp.
dF
SSTB
RGT.A
Suction Gas Temp Circ A
dF
RGTA
DT.A1
A1 Discharge Temperature
dF
DTA1
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
AIR.P
AIR PRESSURES
SP
Static Pressure
" H2O
SP
BP
Building Pressure
" H2O
BP
REF.P
REFRIGERANT PRESSURES
DP.A
Cir A Discharge Pressure
PSIG
DP_A
SP.A
Cir A Suction Pressure
PSIG
SP_A
DP.B
Cir B Discharge Pressure
PSIG
DP_B
SP.B
Cit B Suction Pressure
PSIG
SP_B
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
OHSP
Occupied Heat Setpoint
40-99
dF
OHSP
68
OCSP
Occupied Cool Setpoint
40-99
dF
OCSP
75
UHSP
Unoccupied Heat Setpoint
40-99
dF
UHSP
55
UCSP
Unoccupied Cool Setpoint
40-110
dF
UCSP
90
GAP
Heat-Cool Setpoint Gap
2-10
deltaF
HCSP_GAP
5
V.C.ON
VAV Occ. Cool On Delta
0-25
deltaF
VAVOCON
3.5
V.C.OF
VAV Occ. Cool Off Delta
1-25
deltaF
VAVOCOFF
2
SASP
Supply Air Setpoint
45-75
dF
SASP
55
SA.HI
Supply Air Setpoint Hi
45-75
dF
SASP_HI
55
SA.LO
Supply Air Setpoint Lo
45-75
dF
SASP_LO
60
SA.HT
Heating Supply Air Setpt
80-120
dF
SASPHEAT
85
T.PRG
Tempering Purge SASP
-20-80
dF
TEMPPURG
50
T.CL
Tempering in Cool SASP
5-75
dF
TEMPCOOL
5
T.V.OC
Tempering Vent Occ SASP
-20-80
dF
TEMPVOCC
65
T.V.UN
Tempering Vent Unocc. SASP
-20-80
dF
TEMPVUNC
50
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...