Table 95 — Auto View of Run Status Display Table
Table 96 — Economizer Run Status Display Table
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
VIEW
AUTO VIEW OF RUN STATUS
HVAC
ascii string spelling out the hvac modes
string
OCC
Occupied ?
YES/NO
OCCUPIED
forcible
MAT
Mixed Air Temperature
dF
MAT
EDT
Evaporator Discharge Tmp
dF
EDT
LAT
Leaving Air Temperature
dF
LAT
EC.C.P
Economizer Control Point
dF
ECONCPNT
ECN.P
Economizer Act.Curr.Pos.
0 to 100
%
ECONOPOS
EC2.P
Economzr2 Act.Curr.Pos.
0 to 100
%
ECON2POS
CL.C.P
Cooling Control Point
dF
COOLCPNT
C.CAP
Current Running Capacity
CAPTOTAL
CL.ST
Requested Cool Stage
CL_STAGE
HT.C.P
Heating Control Point
dF
HEATCPNT
HT.ST
Requested Heat Stage
HT_STAGE
H.MAX
Maximum Heat Stages
HTMAXSTG
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
ECON
ECONOMIZER RUN STATUS
ECN.P
Economizer Act.Curr.Pos.
0 to 100
%
ECONOPOS
EC2.P
Economzr2 Act.Curr.Pos.
0 to 100
%
ECON2POS
ECN.C
Economizer Act.Cmd.Pos.
0 to 100
%
ECONOCMD
forcible
ACTV
Economizer Active ?
YES/NO
ECACTIVE
DISA
ECON DISABLING CONDITIONS
UNV.1
Econ Act. Unavailable?
YES/NO
ECONUNAV
UNV.2
Econ2 Act. Unavailable?
YES/NO
ECN2UNAV
ENTH
Enth. Switch Read High ?
YES/NO
ENTH
DBC
DBC - OAT Lockout?
YES/NO
DBC_STAT
DEW
DEW - OA Dewpt.Lockout?
YES/NO
DEW_STAT
DDBC
DDBD- OAT > RAT Lockout?
YES/NO
DDBCSTAT
OAEC
OAEC- OA Enth Lockout?
YES/NO
OAECSTAT
DEC
DEC - Diff.Enth.Lockout?
YES/NO
DEC_STAT
EDT
EDT Sensor Bad?
YES/NO
EDT_STAT
OAT
OAT Sensor Bad ?
YES/NO
OAT_STAT
FORC
Economizer Forced ?
YES/NO
ECONFORC
SFON
Supply Fan Not On 30s ?
YES/NO
SFONSTAT
CLOF
Cool Mode Not In Effect?
YES/NO
COOL_OFF
OAQL
OAQ Lockout in Effect ?
YES/NO
OAQLOCKD
HELD
Econ Recovery Hold Off?
YES/NO
ECONHELD
DH.DS
Dehumid. Disabled Econ.?
YES/NO
DHDISABL
O.AIR
OUTSIDE AIR INFORMATION
OAT
Outside Air Temperature
dF
OAT
forcible
OA.RH
Outside Air Rel. Humidity
%
OARH
forcible
OA.E
Outside Air Enthalpy
OAE
OA.D.T
OutsideAir Dewpoint Temp
dF
OADEWTMP
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...