192
APPENDIX A — LOCAL DISPLAY TABLES
Table J — MODE — OPERATING MODES
Table K — MODE — ALARMS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
SYS.M
ascii string spelling out the system mode
string
HVAC
ascii string spelling out the hvac modes
string
CTRL
ascii string spelling out the “control type”
string
MODE
MODES CONTROLLING UNIT
OCC
Currently Occupied
ON/OFF
MODEOCCP
T.OVR
Timed Override in Effect
ON/OFF
MODETOVR
DCV
DCV Resetting Min Pos
ON/OFF
MODEADCV
SA.R
Supply Air Reset
ON/OFF
MODESARS
DMD.L
Demand Limit in Effect
ON/OFF
MODEDMLT
T.C.ST
Temp.Compensated Start
ON/OFF
MODETCST
IAQ.P
IAQ Pre-Occ Purge Active
ON/OFF
MODEIQPG
LINK
Linkage Active - CCN
ON/OFF
MODELINK
LOCK
Mech.Cooling Locked Out
ON/OFF
MODELOCK
H.NUM
HVAC Mode Numerical Form
number
MODEHVAC
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
CURR
CURRENTLY ACTIVE ALARMS
this is a dynamic list of active alarms
strings
R.CUR
Reset All Current Alarms
YES/NO
ALRESET
ram config
HIST
ALARM HISTORY
this is a record of the last 20 alarms
strings
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...