184
*The display text changes depending on the remote switch configuration (
Configuration
UNIT
RM.CF
). If
RM.CF
is set to 0 (No Remote Switch), then the display text will
be “On” or “Off.” If
RM.CF
is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If
RM.CF
is set to 2 (Start/Stop), then the dis-
play text will be “Stop” or “Start.” If
RM.CF
is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”
APPENDIX A — LOCAL DISPLAY TABLES
Table F — MODE — INPUTS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
GEN.I
GENERAL INPUTS
FLT.S
Filter Status Input
DRTY/CLN
FLTS
forcible
G.FAN
Fan Request From IGC
ON/OFF
IGCFAN
REMT
Remote Input State
*
RMTIN
forcible
ENTH
Enth. Switch Read High ?
YES/NO
ENTH
forcible
S.FN.S
Supply Fan Status Switch
ON/OFF
SFS
forcible
FRZ.S
Freeze Status Switch
ALRM/NORM
FRZ
forcible
PP.SW
Plenum Press.Safety Sw.
HIGH/LOW
PPS
forcible
DL.S1
Demand Limit Switch 1
ON/OFF
DMD_SW1
forcible
DL.S2
Demand Limit Switch 2
ON/OFF
DMD_SW2
forcible
DH.IN
Dehumidify Switch Input
ON/OFF
DHDISCIN
forcible
FD.BK
COMPRESSOR FEEDBACK
HPS.A
Circ A High Press. Switch
HIGH/LOW
CIRCAHPS
HPS.B
Circ B High Press. Switch
HIGH/LOW
CIRCBHPS
CS.A1
Compressor A1 Feedback
ON/OFF
CSB_A1
CS.A2
Compressor A2 Feedback
ON/OFF
CSB_A2
CS.A3
Compressor A3 Feedback
ON/OFF
CSB_A3
CS.B1
Compressor B1 Feedback
ON/OFF
CSB_B1
CS.B2
Compressor B2 Feedback
ON/OFF
CSB_B2
CS.B3
Compressor B3 Feedback
ON/OFF
CSB_B3
STAT
THERMOSTAT INPUTS
G
Thermostat G Input
ON/OFF
G
forcible
W1
Thermostat W1 Input
ON/OFF
W1
forcible
W2
Thermostat W2 Input
ON/OFF
W2
forcible
Y1
Thermostat Y1 Input
ON/OFF
Y1
forcible
Y2
Thermostat Y2 Input
ON/OFF
Y2
forcible
FIRE
FIRE-SMOKE INPUTS
FSD
Fire Shutdown Input
ALRM/NORM
FSD
forcible
PRES
Pressurization Input
ALRM/NORM
PRES
forcible
EVAC
Evacuation Input
ALRM/NORM
EVAC
forcible
PURG
Smoke Purge Input
ALRM/NORM
PURG
forcible
REL.H
RELATIVE HUMIDITY
OA.RH
Outside Air Rel. Humidity
%
OARH
forcible
OA.EN
Outdoor Air Enthalpy
OAE
OA.DP
Outside Air Dewpoint Temp
dF
OADEWTMP
RA.RH
Return Air Rel. Humidity
%
RARH
forcible
RA.EN
Return Air Enthalpy
RAE
SP.RH
Space Relative Humidity
%
SPRH
forcible
SP.EN
Space Enthalpy
SPE
AIR.Q
AIR QUALITY SENSORS
IAQ.I
IAQ - Discrete Input
HIGH/LOW
IAQIN
forcible
IAQ
IAQ - PPM Return CO2
IAQ
forcible
OAQ
OAQ - PPM Return CO2
OAQ
forcible
DAQ
Diff.Air Quality in PPM
DAQ
IQ.P.O
IAQ Min.Pos. Override
%
IAQMINOV
forcible
CFM
CFM SENSORS
O.CFM
Outside Air CFM
CFM
OACFM
R.CFM
Return Air CFM
CFM
RACFM
S.CFM
Supply Air CFM
CFM
SACFM
D.CFM
Fan Track Control D.CFM
CFM
DELTACFM
RSET
RESET INPUTS
SA.S.R
Supply Air Setpnt. Reset
^F
SASPRSET
forcible
SP.RS
Static Pressure Reset
SPRESET
forcible
4-20
4-20 MILLIAMP INPUTS
IAQ.M
IAQ Milliamps
ma
IAQ_MA
OAQ.M
OAQ Milliamps
ma
OAQ_MA
SP.R.M
SP Reset milliamps
ma
SPRST_MA
DML.M
4-20 ma Demand Signal
ma
DMDLMTMA
forcible
EDR.M
EDT Reset Milliamps
ma
EDTRESMA
ORH.M
OARH Milliamps
ma
OARH_MA
SRH.M
SPRH Milliamps
ma
SPRH_MA
RRH.M
RARH Milliamps
ma
RARH_MA
SAC.M
SACFM Milliamps
ma
SACFM_MA
SA.M.T
Supply Air CFM Trim (ma)
-2.0
2.0
SAMATRIM
RAC.M
RACFM Milliamps
ma
RACFM_MA
RA.M.T
Return Air CFM Trim (ma)
-2.0
2.0
RAMATRIM
config
OAC.M
OACFM Milliamps
ma
OACFM_MA
OA.M.T
Outside Air CFM Trim(ma)
-2.0
2.0
OAMATRIM
config
BP.M
BP Milliamps
ma
BP_MA
BP.M.T
Bldg. Pressure Trim (ma)
-2.0
2.0
BPMATRIM
config
SP.M
SP Milliamps
ma
SP_MA
SP.M.T
Static Press. Trim (ma)
-2.0
2.0
SPMATRIM
config
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...