APPENDIX A — LOCAL DISPLAY TABLES
Table H — MODE — CONFIGURATION
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
1 to 4 (multi-text strings)
CTRLTYPE
4
33, 41, 44-47, 49-52, 56, 60-
62, 80, 88, 90, 99
SIZE
Unit Size (30-100)
30 to 100
UNITSIZE
30
44, 45, 46, 51
FN.MD
Fan Mode (0=Auto, 1=Cont)
0 to 1 (multi-text strings)
FAN_MODE
1
33, 44, 45
RM.CF
Remote Switch Config
0 to 3 (multi-text strings)
RMTINCFG
0
39, 44, 45, 99
CEM
CEM Module Installed
Yes/No
CEM_BRD
No
44, 45, 118
TCS.C
Temp.Cmp.Strt.Cool Factr
0 to 60
min
TCSTCOOL
0
44, 45, 93
TCS.H
Temp.Cmp.Strt.Heat Factr
0 to 60
min
TCSTHEAT
0
44, 45, 93
SFS.S
Fan Fail Shuts Down Unit
Yes/No
SFS_SHUT
No
44, 45, 72, 127
SFS.M
Fan Stat Monitoring Type
0 to 2 (multi-text strings)
SFS_MON
0
44, 45, 72, 127
VAV.S
VAV Unocc.Fan Retry Time
0 to 720
min
SAMPMINS
50
44, 45
50.HZ
50 Hertz Unit ?
Yes/No
UNIT_HZ
No
44, 45, 46, 51
MAT.S
MAT Calc Config
0 to 2 (multi-text strings)
MAT_SEL
1
44, 45, 54
MAT.R
Reset MAT Table Entries?
Yes/No
MATRESET
No
44, 45, 54
MAT.D
MAT Outside Air Default
0 -100
%
MATOAPOS 20
44, 45
ALTI
Altitude……..in feet:
0 to 60000
ALTITUDE
0
44, 45
DLAY
Startup Delay Time
0 -900
secs
DELAY
0
44, 46
AUX.R
Auxiliary Relay Config
0 to 3 (multi-text strings)
AUXRELAY
0
44, 46
SENS
INPUT SENSOR CONFIG
SENS
SPT.S
Space Temp Sensor
Enable/Disable
SPTSENS
Disable
33, 44, 46
SENS
SP.O.S
Space Temp Offset Sensor
Enable/Disable
SPTOSENS
Disable
44, 46, 99
SENS
SP.O.R
Space Temp Offset Range
1 to 10
SPTO_RNG
5
44, 46, 99
SENS
SRH.S
Space Air RH Sensor
Enable/Disable
SPRHSENS
Disable
44, 45, 46, 88
SENS
RRH.S
Return Air RH Sensor
Enable/Disable
RARHSENS
Disable
44, 45, 46, 77, 88, 95, 126
SENS
FLT.S
Filter Stat.Sw.Enabled ?
Enable/Disable
FLTS_ENA
Disable
44, 46, 72
COOL
COOLING CONFIGURATION
A1.EN
Enable Compressor A1
Enable/Disable
CMPA1ENA
Enable
47, 48
A2.EN
Enable Compressor A2
Enable/Disable
CMPA2ENA
Enable
47, 48
A3.EN
Enable Compressor A3
Enable/Disable
CMPA3ENA
Enable
47, 48
B1.EN
Enable Compressor B1
Enable/Disable
CMPB1ENA
Enable
47, 48
B2.EN
Enable Compressor B2
Enable/Disable
CMPB2ENA
Enable
47, 48
B3.EN
Enable Compressor B3
Enable/Disable
CMPB3ENA
Enable
47, 48
CS.A1
CSB A1 Feedback Alarm
Enable/Disable
CSB_A1EN
Enable
48
CS.A2
CSB A2 Feedback Alarm
Enable/Disable
CSB_A2EN
Enable
48
CS.A3
CSB A3 Feedback Alarm
Enable/Disable
CSB_A3EN
Enable
48
CS.B1
CSB B1 Feedback Alarm
Enable/Disable
CSB_B1EN
Enable
48
CS.B2
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
Enable
48
CS.B3
CSB B3 Feedback Alarm
Enable/Disable
CSB_B3EN
Enable
48
Z.GN
Capacity Threshold Adjst
0.1 to 10.0
Z_GAIN
1
48, 52, 53, 54, 116
MC.LO
Compressor Lockout Temp
-25 to 55
dF
OATLCOMP
40
48, 54
LLAG
Lead/Lag Configuration
0, 1, 2
LEAD_LAG
0
48
M.M.
Motor Master Control ?
Yes/No
MOTRMAST No
48, 49, 56
SCT.H
Maximum Condenser Temp
100 to 150
dF
SCT_MAX
115
48, 49, 56
SCT.L
Minimum Condenser Temp
40 to 90
dF
SCT_MIN
72
48, 49, 56
DG.A1
A1 is Digital Scroll
Yes/No
DIGCMPA1
No
48, 49
MC.A1
A1 Min Digital Capacity
10 to 100
%
MINCAPA1
50
48, 49
DS.AP
Dig Scroll Adjust Delta
0 -100
%
DSADJPCT
100
48, 49
DS.AD
Dig Scroll Adjust Delay
15 to 60
sec
DSADJDLY
20
48, 49
DS.RP
Dig Scroll Reduce Delta
0 -100
%
DSREDPCT
6
48, 49
DS.RD
Dig Scroll Reduce Delay
15 to 60
sec
DSREDDLY
30
48, 49
DS.RO
Dig Scroll Reduction OAT
70-120
dF
DSREDOAT
95
48, 49
DS.MO
Dig Scroll Max Only OAT
70-120
dF
DSMAXOAT
105
48, 49
MLV
Min Load Valve Enable
Enable/Disable
MLV_ENAB
Disable
48, 49, 99
H.SST
Hi SST Alert Delay Time
5 to 30
min
HSSTTIME
10
48, 49, 124
RR.VF
Rev Rotation Verified?
Yes/No
REVR_VER
No
48, 49, 124
CS.HP
Use CSBs for HPS Detect?
Yes/No
CSBHPDET
Yes
48, 49
EDT.R
EVAP.DISCHRGE TEMP RESET
RS.CF
EDT Reset Configuration
0 to 3 (multi-text strings)
EDRSTCFG
2
33, 39, 47, 122
RTIO
Reset Ratio
0 to 10
RTIO
3
33, 47
LIMT
Reset Limit
0 to 20
deltaF
LIMT
10
33, 47
RES.S
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
33, 45, 47
HEAT
HEATING CONFIGURATION
HT.CF
Heating Control Type
0 to 5
HEATTYPE
0
60, 61, 62, 63, 64, 65, 68, 69,
89, 90
HT.SP
Heating Supply Air Setpt
80 to 120
dF
SASPHEAT
85
60
OC.EN
Occupied Heating Enabled
Yes/No
HTOCCENA
No
60, 61
LAT.M
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
60, 68
SG.CF
STAGED HEAT CONFIGS
SG.CF
HT.ST
Staged Heat Type
0 to 8
HTSTGTYP
0
60, 63, 64, 65, 66, 67
SG.CF
CAP.M
Max Cap Change per Cycle
5 to 45
HTCAPMAX
45
60, 63, 64
SG.CF
M.R.DB
St.Ht DB min.dF/PID Rate
0 to 5
HT_MR_DB
0.5
60, 63, 64
SG.CF
S.G.DB
St.Heat Temp. Dead Band
0 to 5
^F
HT_SG_DB
2
60, 63, 64
SG.CF
RISE
Heat Rise dF/sec Clamp
0.05 to 0.2
HTSGRISE
0.06
60, 63, 64, 67
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...