232
APPENDIX F — UPC OPEN CONTROLLER
Fig. L — BACview
6
Device Connection
Table AN — LED Status Indicators
Table AO —
Run
and
Error
LEDs Controller and Network Status Indication
LED
STATUS
Power
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on the
incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition that
caused the fault returns to normal.
Rx
Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.
Tx
Lights when the controller transmits data to the network segment; there is an Tx LED for Ports 1 and 2.
Run
Lights based on controller status. See Table AO.
Error
Lights based on controller status. See Table AO.
RUN LED
ERROR LED
STATUS
2 flashes per second
Off Normal
2 flashes, alternating with
Run
LED
Five minute auto-restart delay after system error
3 flashes, then off
Controller has just been formatted
1 flash per second
Controller is alone on the network
On
Exec halted after frequent system errors or control programs halted
5 flashes per second
On
Exec start-up aborted, Boot is running
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second, alternating with
Run
LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second, alternating with
Run
LED Brownout
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...