203
SP__
Static Pressure Control
Enable/Disable
STATICFG
Disable
Staged Air Volume Control
Enable/Disable
STGAVCFG
Disable
Static Pressure Sensor
Enable/Disable
SPSENS
Disable
Static Press. Low Range
-10 to 0
SP_LOW
0
Static Press. High Range
0 to 10
SP_HIGH
5
Static Pressure Setpoint
0 to 5
" H2O
SPSP
1.5
VFD Minimum Speed
0 to 100
%
STATPMIN
10
VFD Maximum Speed
0 to 100
%
STATPMAX
100
VFD Fire Speed Over.
0 to 100
%
STATPFSO
100
Stat. Pres. Reset Config
0 to 4 (multi-text strings)
SPRSTCFG
0
SP Reset Ratio
0.00 to 2.00
SPRRATIO
0.20
SP Reset Limit
0.00 to 2.00
SPRLIMIT
0.75
SP Reset Econo. Position
0 to 100
%
ECONOSPR
5
Stat.Pres.PID Run Rate
5 to 120
sec
SPIDRATE
15
Static Press. Prop. Gain
0 to 5
STATP_PG
0.5
Static Press. Intg. Gain
0 to 2
STATP_IG
0.5
Static Press. Derv. Gain
0 to 5
STATP_DG
0.3
SWLG
Filter Status Inpt-Clean
Open/Close
FLTSLOGC
Open
IGC Feedback - Off
Open/Close
GASFANLG
Open
RemSw Off-Unoc-Strt-NoOv
Open/Close
RMTINLOG
Open
Enthalpy Input - Low
Open/Close
ENTHLOGC
Close
Fan Status Sw. - Off
Open/Close
SFSLOGIC
Open
Dmd.Lmt.Sw.1 - Off
Open/Close
DMD_SW1L
Open
Dmd.Lmt.Sw.2 - Off
Open/Close
DMD_SW2L
Open
IAQ Disc.Input - Low
Open/Close
IAQINLOG
Open
Fire Shutdown - Off
Open/Close
FSDLOGIC
Open
Press. Switch - Off
Open/Close
PRESLOGC
Open
Evacuation Sw. - Off
Open/Close
EVACLOGC
Open
Smoke Purge Sw. - Off
Open/Close
PURGLOGC
Open
Dehumidify Sw. - Off
Open/Close
DHDISCLG
Open
T24_CFG
Economizer Installed ?
Yes/No
ECON_ENA
Yes
Econ.Act.2 Installed ?
Yes/No
ECON_TWO
No
SAT Settling Time
secs
SAT_SET
240
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
Log Title 24 Faults
Yes/No
T24LOGFL
No
T24 Econ Move Detect
%
T24ECMDB
1
T24 Econ Move SAT Test
%
T24ECSTS
10
T24 Econ Move SAT Change
deltaF
T24SATMD
0.2
T24 Econ RAT-OAT Diff
deltaF
T24RATDF
15
T24 Heat/Cool End Delay
mins
T24CHDLY
25
T24 Test Minimum Pos.
%
T24TSTMN
15
T24 Test Maximum Pos.
%
T24TSTMX
85
Economizer Deadband Temp
dF
AC_EC_DB
5
Econ Fault Detect Gap
%
EC_FLGAP
5
Econ Fault Detect Timer
secs
EC_FLTMR
20
Excess Air CFM
CFM
EX_ARCFM
150
Excess Air Detect Timer
secs
EX_ARTMR
800
T24 Econ Auto-Test Day
T24_ECDY
0
T24 Econ Auto-Test Time
T24_ECTM
2
T24 AutoTest SF Run Time
mins
T24ACMRT
2
T24 Auto-Test VFD Speed
%
T24ACSPD
20
T24 Auto-Test Econ % Opn
%
T24ACOPN
50
T24 Auto-Test VFD % Chng
%
T24VFDPC
10
APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
DEFAULT
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...