62-11637
5–22
MAX THROTTLE POSI-
TION
80 - 125
120
default
IF THIS CONFIGURATION IS AVAILABLE, USE
FACTORY DEFAULT ONLY, DO NOT OPERATE
WITH A DIFFERENT SETTING.
ALARM SETTINGS
OUT OF RANGE SHUT-
DOWN
YES /
NO
YES = When the refrigerated compartment tempera-
ture has been out-of-range for 45 minutes, the alarm
light will come on, and the unit will shut down.
NO = When the refrigerated compartment tempera-
ture has been out-of-range for 30 minutes, the alarm
light will come on and the unit will continue to run.
Refer to Alarm A00053 - “BOX TEMPERATURE
OUT OF RANGE” (
RPM ALARM SHUTDOWN
YES
/ NO
YES = When the A00039 - “CHECK ENGINE RPM”
alarm is activated the alarm light will illuminate and
the engine will shut down.
NO = When the A00039 - “CHECK ENGINE RPM”
alarm is activated the alarm light will illuminate and
the engine will continue to run.
LOW PRESSURE SHUT-
DOWN
YES
/ NO
YES = When the A00018 - “LOW REFRIGERANT
PRESSURE” alarm is activated the alarm light will il-
luminate and the unit will shut down.
NO = When the A00018 - “LOW REFRIGERANT
PRESSURE” alarm is activated the alarm light will il-
luminate and the unit will continue to run.
• LP SHUTDOWN DELAY
(0 - 255 seconds in 1 second
increments)
120 SECS
If the Low Pressure Shutdown Configuration is set to
YES, shutdown is to be delayed for this amount of
time after the Low Pressure Shutdown signal is re-
ceived.
HIGH SUCT PRESS SHUT-
DOWN
YES
/ NO
YES = When the A00027 - “HIGH SUCTION PRES-
SURE” alarm is activated the alarm light will illumi-
nate and the unit will shut down.
NO = When the A00027 - “HIGH SUCTION PRES-
SURE” alarm is activated the alarm light will illumi-
nate and the unit will continue to run.
REFRIGERATION SYS
SHUTDOWN
YES
/ NO
YES = When the A00028 - “CHECK REFRIGERA-
TION SYSTEM” alarm is activated the alarm light will
illuminate and the unit will shut down.
NO = When the A00028 - “CHECK REFRIGERA-
TION SYSTEM” alarm is activated the alarm light will
illuminate and the unit will continue to run.
COMPRESSOR ALARM
SHUTDOWN
(This Configuration is an op-
tion, it will not display if the
option is not installed.)
YES
/ NO
If the “Compressor Alarm Shutdown” option has
been installed (refer to Unit Data), this setting will be
available.
YES = The unit will shutdown and not restart when
Alarm 13, 17, 18, 27, 28 or 56 occur 3 times within 2
hours of continuous engine operation.
NO = Normal shutdown rules for above alarms.
Table 5–1 Configuration Settings
Configuration
Selections
Description