62-11637
3–22
RESTART
TEMPERATURE
5 to 18°F (0.28 to
10°C) (in 0.5° incre-
ments)
5.4°F (3°C)
Following the Minimum Off Time, should a compartment tem-
perature drift this far above or below setpoint in the Perishable
Range or above setpoint in the Frozen Range, the unit will re-
start.
OVERRIDE
TEMPERATURE:
3.6 to 18°F (2 to1 0°C)
(in 0.5 degree incre-
ments)
3.6°F (2.0°C)
This selects the override temperature for the Minimum Off
Time portion of the Auto Start-Stop Off Cycle. During the Min-
imum Off Time, should the refrigerated compartment tem-
perature drift this far above or below setpoint in the Perishable
Range, or above setpoint in the Frozen Range, the unit will
override the Minimum Off Time, and restart.
MAXIMUM OFF TIME:
OFF
10MINS
TO
255MINS (in 1 minute
increments)
OFF - There is no maximum off time.
When a minute value is selected, this is the longest amount
of time the unit will remain off during a (Perishable or Frozen
or both) Auto Start/Stop Off Cycle. When this time expires, the
unit will restart and run for the Minimum Run Time, regardless
of any temperature change inside the compartment.
FROZEN SHUTDOWN
OFFSET:
0°F
to 1.1°F
(
0°C
to 0.6°C) (in 0.1°F
or C increments)
This only applies to Frozen Setpoints in Start-Stop operation.
This offset is the number of degrees below setpoint that the
unit will run before cycling off. This will allow for a lower aver-
age compartment temperature when considering temperature
rises during off cycles.
SLEEP MODE
For complete instructions on entering and setting parameters for Sleep Mode refer to
OVERRIDES
OVERRIDE
REMOTE SWITCH
1 SHUTDOWN
(REMS1)
AND
OVERRIDE DOOR
SWITCH
SHUTDOWN (DS)
NO
YES
If the switches are all configured “Switch Not Installed”, this
parameter will not display.
NO = the system will respond to the switch as configured.
YES = the configured action on activation of the switch will be
overridden and the action will be alarm only. The purpose of
this setting to temporarily override the Configuration setting in
situations where shutdown or speed change is not desired.
VIEWING PREFERENCES
DISPLAY
TEMPERATURE IN
°F
°C
Temperatures will display in either Fahrenheit (°F) or Celsius
(°C). (for North American Units, this function may be locked)
DISPLAY
PRESSURE IN
PSIG
BAR
Pressure will display in either psig or (bar).
(for North American Units, this function may be locked)
DATE FORMAT
MM/DD/YYYY
DD/MM/YYYY
Date will display in either US (MM/DD/YYYY) or European
(DD/MM/YYYY) format.
ALARM
DESCRIPTIONS
YES
NO
YES = In the Driver Mode, the alarm code and alarm descrip-
tion will be displayed.
NO = In the Driver Mode, only the alarm code will be dis-
played.
CONTRAST
0 TO 63 (In single
digit increments)
35
Higher numbers increase the contrast of the display screen.
Table 3–2 Functional Parameters
FUNCTION
PARAMETER
SELECTIONS
DESCRIPTION