6 : Alarm status
w
Normal (no alarm)
w
Partial (alarm but unit is not down)
w
Shutdown (unit is down)
7: Active Demand Limit Value. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the external limit switch contact and whatever the value of the demand limit switch setpoint.
If the unit is not in CCN mode the forced value shall be unused. Forced value and force code shall appear in the
GENUNIT Points Display table only if the unit is under CCN control.
8: Control Point. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead of the
real control point calculation. If the unit is not in CCN mode the forced value shall be unused. Forced value and
force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control.
9 : Active all the time even if the unit is not in CCN control type.
10: Heat Reclaim Select. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the remote reclaim switch. Forced value and force code shall appear in the GENUNIT
Points Display table only if the unit is under CCN control.
DISPLAY SCREEN
TABLE NAME: CIRCA_AN PIC TABLE TYPE : 11H, instance 2
DESCRIPTION
STATUS
UNITS
POINTS
FORCEABLE
1
CIRCUIT A ANALOG VALUES
2.
3
Percent Total Capacity
0 - 100
%
CAPA_T
N
4
Discharge Pressure
nnn.n
psi
DP_A
N
5
Suction Pressure
nnn.n
psi
SP_A
N
6
Oil Pressure Cp1
nnn.n
psi
CPA1_OP
N
7
Oil Pressure Cp2
nnn.n
psi
CPA2_OP
N
8
Oil Press Difference Cp1
nnn.n
psi
DOP_A1
N
9
Oil Press Difference Cp2
nnn.n
psi
DOP_A2
N
10
Economizer Pressure Cp1
nnn.n
psi
CPA1_ECP
N
11
Economizer Pressure Cp2
nnn.n
psi
CPA2_ECP
N
12
Saturated Condensing Tmp
±nnn.n
°F
SCT_A
N
13
Saturated Suction Temp
±nnn.n
°F
SST_A
N
14
Discharge Gas Temp Cp 1
±nnn.n
°F
CPA1_DGT
N
15
Discharge Gas Temp Cp 2
±nnn.n
°F
CPA2_DGT
N
16
Average Discharge Gas Tp
±nnn.n
°F
dt_a
N
17
Motor Temperature Comp 1
±nnn.n
°F
CPA1_TMP
N
18
Motor Temperature Comp 2
±nnn.n
°F
CPA2_TMP
N
19
Motor Current Comp 1
nnn.n
AMPS
CPA1_CUR
N
20
Motor Current Comp 2
nnn.n
AMPS
CPA2_CUR
N
21
EXV Position
0 - 100
%
EXV_A
N
22
Head Press Actuator Pos
0 - 100
%
hd_pos_a
N
23
Cooler Exchange Delta T
n.n
^F
PINCH_A
N
24
Motor Cool TQ in Kohms
nn.n
MTQ_RESA
N
25
Motor Cooling Puls Cycle
nnn
CPA1_PUL
N
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 62/98
©