CONFIGURATION SCREEN
TABLE NAME: USER PIC TABLE TYPE : 10H, instance 2
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
1
USER CONFIGURATION
2
3
Circuit Loading Sequence
0/1/2
0
-
lead_cir
4
0 = Auto
5
1 = Circuit A First
6
2 = Circuit B First
7
Loading Sequence
0/1
0
-
seq_typ
8
9
Ramp Loading Select
Yes/No
No
-
ramp_sel
10
11
Unit Off to On Delay
1 to 15
1
min
off_on_d
12
13
Cooler Pumps Sequence
0/1/2/3/4
0
-
pump_seq
14
0 = No Pump
15
1 = One Pump Only
16
2 = Two Pumps Auto
17
3 = Pump#1 Manual
18
4 = Pump#2 Manual
19
Pump Auto Rotation Delay
24 to 3000
48
hours
pump_del
20
Periodic Pumps Start
Yes/No
No
-
pump_per
21
22
Reset Type Select
0 to 3
0
-
res_sel
23
0 = None
24
1 = Voltage Control
25
2 = Delta T Control
26
3 = OAT Control
27
28
Demand Limit Type Select
0 to 2
0
-
lim_sel
29
0 = None
30
1 = Switch Control
31
2 = 0-10vdc Control
32
Vdc For 100% Demand Lim
0 to 10
0
volts
lim_mx
33
Vdc For 0% Demand Limit
0 to 10
10
volts
lim_ze
34
35
Night Control
36
Start Hour
00:00 to 24:00
00:00
-
nh_start
37
End Hour
00:00 to 24:00
00:00
-
nh_end
38
Capacity Limit
0 to 100
100
%
nh_limit
39
Capacity Limit
0 to 100
100
%
nh_limit
40
41
Chiller Comp Current Limit
90 to 1500
1
1500
amps
curr_lim
42
Menu Description Select
Yes/No
Yes
-
menu_des
43
Pass For All User Config
Yes/No
No
-
all_pass
1. Refer to control capacity override #35, chiller current limit description
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 68/98
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION
Downloaded from
www.Manualslib.com
manuals search engine