S-A
-
Circuit A & B Oil level indicator :
3 = Circuit A & Circuit B oil level are both high
2 = Circuit A oil level is high, circuit B oil level is low
1 = Circuit A oil level is low, circuit B oil level is high
0 = Circuit A & Circuit B oil level are both low
TOT_OIL
S-A
-
Unit state information (int value):
1 = local operating type, off mode
2 = local operating type, on mode
3 = remote operating type, off mode
4 = remote operating type, on mode
5 = ccn operating type, off mode
6 = ccn operating type, on mode
7 = ccn operating type, off mode, system manager control
8 = ccn operating type, on mode, system manager control
9 = Master operating type, off mode
10 = Master operating type, on mode
11 = Master operating type, Master Slave Control, off mode
12 = Master operating type, Master Slave Control, on mode
off mode = unit is commended to OFF or totally failed
on mode = unit is commended to ON (status could also be
delay)
STATE
S-A
°F
Saturated Suction Temperature, Circuit B
SST_B
S-A
°F
Saturated Suction Temperature, Circuit A
SST_A
S-D
Setpoint occupancy status
SP_OCC
S-A
-
Sum/Z Value for capacity PID Loop Control
SMZ
S-A
°F
Saturated Condensing Temperature, Circuit B
SCT_B
S-A
°F
Saturated Condensing Temperature, Circuit A
SCT_A
S-D
-
Servicing alert Reset
S RESET
S-D
-
Rotate pumps now
ROT PUMP
S-D
-
Reclaim Select
RECL_SEL
S-A
^F
Cooler Exchange Deltat T circuit B
PINCH_B
S-A
^F
Cooler Exchange Deltat T circuit A
PINCH_A
S-A
min
Minutes left for start
MIN_LEFT
TYPE
UNITS
DESCRIPTIONS
POINT NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 82/98
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION