4.2.4.7 - Service 4 configuration table from Service Tool
The Network Service tool allows to view and modify the service configuration table
UPDTHOUR
. Unit should be
stopped and under CCN Operating Type control.
TABLE NAME: UPDTHOUR PIC TABLE TYPE : 13H, instance 3
DESCRIPTION
STATUS
UNITS
POINT
1
TABLE TO BE USED FOR RUN
2
TIMES & STARTS UPDATE IN
3
CASE OF CONTROL RETROFIT
4
5
Machine Operating Hours
nnnnn
hours
hr_mach
6
Machine Starts
nnnnn
-
st_mach
7
Compressor A1 Hours
nnnnn
hours
hr_cp_a1
8
Compressor A2 Hours
nnnnn
hours
hr_cp_a2
9
Compressor A1 Starts
nnnnn
-
st_cp_a1
10
Compressor A2 Starts
nnnnn
-
st_cp_a2
11
Compressor B1 Hours
nnnnn
hours
hr_cp_b1
12
Compressor B2 Hours
nnnnn
hours
hr_cp_b2
13
Compressor B1 Starts
nnnnn
-
st_cp_b1
14
Compressor B2 Starts
nnnnn
-
st_cp_b2
15
Cooler Pump #1 Hours
nnnnn
hours
hr_cpum1
16
Cooler Pump #2 Hours
nnnnn
hours
hr_cpum2
17
Condenser Pump Hours
nnnnn
hours
hr_hpump
Note: this table shall be used for purposes of transplanting the devices on time or starts number in the event of a
module hardware failure or software upgrade via downloading. It shall be usable only if all items are still nul.
Afterwards, its access shall be denied.
4.2.4.8 - Service 4 configuration table from main interface, runtime sub menu
The main interface allows to view and modify the service configuration table UPDTHOUR. Unit shalld be stopped
and service password or factory password are required.
Condenser Pump operating hours. Not displayed if cond_ctr =
0 or recl opt =0 and uni typ =1 or 4
hrs/10 or 100
hr_hpump
15 [1]
Cooler Pump #2 operating hours. Only if pump_seq > 1.
hrs/10 or 100
hr_cpum2
14 [1]
Cooler Pump #1 operating hours. Only if pump seq > 0.
hrs/10 or 100
hr cpum1
13 [1]
Average of Maximum number of compressors starts/hour
during last 24 hours
-
st_cp_av
12
Maximum number of compressors starts during last hour
-
st cp mx
11
Compressor B2 starts (only if cap_b2 > 0)
-/10 or 100
st_cp_b2
10 [1]
Compressor B1 starts (only if cap_b1 > 0)
-/10 or 100
st_cp_b1
9 [1]
Compressor A2 starts (only if cap a2 > 0)
-/10 or 100
st cp a2
8 [1]
Compressor A1 starts
-/10 or 100
st cp a1
7
Machine starts
-/10 or 100
st mach
6
Compressor B2 operating hours (only if cap b2 > 0)
hrs/10 or 100
hr cp b2
5 [1]
Compressor B1 operating hours (only if cap_b1 > 0)
hrs/10 or 100
hr_cp_b1
4 [1]
Compressor A2 operating hours (only if cap_a2 > 0)
hrs/10 or 100
hr_cp_a2
3 [1]
Compressor A1 operating hours
hrs/10 or 100
hr cp a1
2
Machine operating hours
hrs/10 or 100
hr mach
1
When selected this item shall allow to return to the main
menu.
-
0
COMMENTS
UNITS
VARIABLE
ITEM #
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 31 /98
Downloaded from
www.Manualslib.com
manuals search engine