![Carrier Pro-Dialog CONTROL 4 User Manual Download Page 81](http://html1.mh-extra.com/html/carrier/pro-dialog-control-4/pro-dialog-control-4_user-manual_2562390081.webp)
alll
H-DO
-
Critical Alarm Signal, Command
SAFE_ALM
all
H-AI
PSI
Suction pressure, circuit B
SP_B
all
H-AI
PSI
Suction pressure, circuit A
SP_A
recl_opt = yes and
cpb1_mta > 0
H-AI
PSI
Reclaim Pumpdown Pressure circuit B
PD_P_B
recl_opt = yes
H-AI
PSI
Reclaim Pumpdown Pressure circuit A
PD_P_A
unit_typ = 1 or 4 and
cpb1_mta > 0
H-DO
Oil Heater Circuit B
OIL_HTRB
unit_typ = 1 or 4
H-DO
Oil Heater Circuit A
OIL_HTRA
unit_typ = 1 or 4
H-AI
°F
Outside Air Temperature
OAT
heat_sel = yes or
recl_opt = yes
recl_opt = yes
recl_opt = yes
recl_opt = yes
recl_opt = yes
recl_opt = yes
(heat_sel = yes)
(heat_sel = yes)
(heat_sel = yes)
H-DOM
-
NRCP (AQUASNAP) Basic board multilexed DO's,
or AUX 1 Basic board multilexed DO's:
b
9
b
8
b
7
b
6
b
5
b
4
b
3
b
2
b
1
b
0
b
0
:
hr_val_a
reclaim valve circuit A
b
1
:
hr_val_b
reclaim valve circuit B
b
2
:
unused
b
3
:
cond_htr
reclaim condenser heater
b
4
:
pd_val_a
pumpdown valve circuit A
b
5
:
pd_val_b
pumpdown valve circuit B
b
6
:
unused
b
7
:
cool_htr
cooler heater
b
8
:
refa_iso
refriegerant solenoid A
b
9
: refb_iso refriegerant solenoid B
MUX_HRDO
CONFIGURATION
TYPE
UNITS
DESCRIPTIONS
POINT
NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 80/98
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION
Downloaded from
www.Manualslib.com
manuals search engine