4.2.4.5 - Service 3 configuration table from Service Tool
The Network Service tool allows to view and modify the service configuration table
MAINCFG
. Unit should be
stopped and under CCN Operating Type control.
TABLE NAME: MAINTCFG PIC TABLE TYPE : 13H, instance 4
DESCRIPTION
STATUS
DEFAULT
UNITS POINT
1
MAINTENANCE CONFIG
2
3
Servicing Alert
Enable/Disable
Disable
-
s_alert
4
5
Refrigerant Charge Ctrl
Enable/Disable
Disable
-
charge_c
6
Water Loop Control
Enable/Disable
Disable
-
wloop_c
7
Air Exchanger Control
Enable/Disable
Disable
-
aexch_c
8
9
CPump 1 Ctl Delay (days)
0 to 1000
0
-
cpump1_c
10
CPump 2 Ctl Delay (days)
0 to 1000
0
-
cpump2_c
11
HPump Ctrl Delay (days)
0 to 1000
0
hpump_c
12
Water Filter Ctrl (days)
0 to 1000
0
-
wfilte_c
13
A1 Oil Filter Ctl (days)
0 to 1000
0
ofila1_c
14
A2 Oil Filter Ctl (days)
0 to 1000
0
ofila2_c
15
B1 Oil Filter Ctl (days)
0 to 1000
0
ofilb1_c
16
B2 Oil Filter Ctl (days)
0 to 1000
0
ofilb2_c
4.2.4.6 - Service 3 configuration table from main interface
The main interface allows to view and modify the service configuration table MAINCFG. Unit should be stopped
and service password or factory password are required.
Oil filer b2 next service in days (displayed only cap b2 > 0)
-
ofilb2 m
12[1]
Oil filer b1 next service in days (displayed only cap_b1> 0)
-
ofilb1_m
11[1]
Oil filer a2 next service in days (displayed only cap_a2 > 0)
-
ofila2_m
10[1]
Oil filer a1 next service in days.
-
ofila1 m
9[1]
Water filter next service in days.
-
wfilte m
8[1]
Condenser water pump next service in days, (displayed only if recl_opt = yes or
unit typ = 2 or 3 and cond tr > 0)
-
hpump_m
7[1]
Cooler water pump #2 next service in days (displayed only if pump_seq > 1)
-
cpump2_m
6[1]
Cooler water pump #1 next service in days (displayed only if pump_seq > 0)
-
cpump1_m
5[1]
Air exchanger control select
-
aexch m
4[1]
Water loop size control select
-
wloop m
3[1]
Refrigerant charge control select
-
charge m
2[1]
Reset maintenance select.
-
s reset
1
When selected this item shall allow to return to the main menu.
-
0
COMMENTS
UNITS
VARIABLE
ITEM #
This table is used for service maintenance alert and not available today.
©