This decision specifies the amount of time that will be allowed to elapse between alarm retries. Retries occur
when an alarm is not acknowledged by a network alarm acknowledger, which may be either a Building
Supervisor, an Autodial Gateway, or a Dataport 2. If the acknowledgement is not received, the alarm will be
retransmitted after the number of minutes specified in this decision.
Allowable Entries
1 to 240 minutes
Default
10 minutes
REALARM TIME
This decision specifies the amount of time that will be allowed to elapse between re-alarms. A re-alarm
occurs when the condition that caused the initial alarm continues to persist for the number of minutes
specified in this decision. Re-alarming will continue to occur at the specified interval until the condition
causing the alarm is corrected.
Allowable Entries
1 to 254 minutes
Default
30 minutes
ALARM SYSTEM NAME
This decision specifies the system element name that will appear in alarms generated by the Pro-Dialog
control.
Allowable Entries
Up to 8 alphanumeric characters
Default
PRO_30GX
©