4.2.3.2- Factory configuration from main interface
Economizer units with TQ feedback signal sensor
-
yes/no
tq r fbk
19
Pro dialog 4 Aux boards select
-
yes/no
pd4 aux
18
EXV A Maximum Steps Number (Shall be left 1500)
-
1500 to 15000
exva_max
17
EXV A Maximum Steps Number (Shall be left 1500)
-
1500 to 15000
exva_max
16
Cooler heater select displayed on air cooled chiller only
-
yes/no
heat sel
15[1]
Cooler leaving sensor on circuit A select
-
yes/no
cira lwt
14
Cooler number of pass select
-
1 to 3
evap pas
13
Heat reclaim option select
-
yes/no
recl opt
12[1]
Reclaim sensors select
-
yes/no
hr_temp
11[1]
Compressor B2 Must Trip Amps.
amps
0 to 560
cpb2_mta
10[1]
Compressor B1 Must Trip Amps.
amps
0 to 560
cpb1 mta
9[1]
Compressor A2 Must Trip Amps.
amps
0 to 560
cpa2 mta
8[1]
Compressor A1 Must Trip Amps
amps
0 to 560
cpa1 mta
7
Large Band Oil transducer select
-
yes/no
oil sel
6
Economizer select
-
yes/no
econ_sel
5
Varifan or Water valve select
-
0,1,2,3,4
hd_selec
4
Number of fans on circuit B not controlled by a varifan
-
0 to 8
nb fan b
3[1]
Number of fans on circuit A not controlled by a varifan
-
0 to 8
nb fan a
2[1]
Chiller type select
-
1/2,3,4
unit typ
1
When selected this item shall allow to return to the Configuration
main menu.
-
"FACTORY
MEnu"
-
0
COMMENTS
UNITS
FORMAT
VARIABLE
ITEM #
Factory password
-
0 to 150
fac_pass
1
When selected this item shall allow to return to the Configuration
main menu.
-
"FACTORY 2
MEnu"
-
0
COMMENTS
UNITS
FORMAT
VARIABLE
ITEM #
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original