4.2.6.4 - Pro-Dialog alarm configuration table
The Pro-Dialog control has an alarm configuration table associated with it: ALARMDEF. This table can be
accessed through the Modify Controller menu of the Network Service Tool. This table needs to be configured
only if the unit is network connected to a Building Supervisor, an Autodial Gateway or a Dataport 2, and only if
these options are configured to receive network alarms.
The parameters which are configured in this table determine the handling of alarms.
TABLE NAME: ALARMDEF PIC TABLE TYPE : 14H,
instance 4
DESCRIPTION
STATUS
DEFAULT
POINT
1
Alarm Routing Control
0-11111111
00000000
ALRM_CNT
2
Alarm Equipment Priority
0 - 7
4
EQP_TYP
3
Comm Failure Retry Time
1 - 240 min
10
RETRY_TM
4
Realarm Time
1 - 255 min
30
RE_ALARM
5
Alarm System Name
8 chars
PD4_GXHX
ALRM_NAM
ALARMDEF Decisions description:
ALARM ROUTING CONTROL
This decision determines which CCN system elements will receive and process alarms sent by the
Pro-Dialog. Input for the decision consists of eight digits, each of which can be set to either 0 or 1. Setting a
digit to 1 specifies that alarm will be sent to the system element that correspond to that digit. Setting all digits
to 0 disables alarm processing. Digits in this decision correspond to CCN elements in the following manners:
Note: If the CCN network does not contain a Building Supervisor, Autodial Gateway, or Dataport 2 to
serve as an alarm acknowledger, all digits in this decision shall be set to 0 in order to prevent
unnecessary activity on the CCN communication bus.
Allowable Entries
0 = Disabled
1 = Enabled
Default
00000000
ALARM EQUIPMENT PRIORITY
A Building Supervisor uses the value in this decision when sorting alarms by level. Within any group of
alarms that all have the same level, the Building Supervisor sorts alarms according to Alarm Equipment
Priority.
Allowable Entries
0 to 7 (priority numbers)
Default
4
COMM FAILURE RETRY TIME
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 33 /98
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
Local Building
Supervisor(s)
Autodial Gateway(s)
Dataport 2