4.2.4.3 - Service 2 configuration table from Service Tool
The Network Service tool allows to view and modify the service configuration table SERVICE2. Unit shall be
stopped and under CCN Operating Type control.
TABLE NAME: SERVICE2 PIC TABLE TYPE : 13H, instance 2
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
1
Condenser Pump Ctrl Type
0/1/2
1
0
-
cond_ctr
2
Condenser Fluid Type
1/2/3
2
1
-
cond_typ
3
Cooler Lowest Setpoint
- 20 to 101
3
14
^F
low_setp
4
Cooler Heater Delta Spt
0.6 to 3.3
4
1.1
^C
heatersp
5
CCN/Clock Functions
Enable/Disable
5
Enable
-
ccnclock
6
Auto Start When SM Lost
Enable/Disable
6
Disable
-
auto_sm
7
8
RECLAIM PARAMETERS
9
Reclaim to Reclaim Delay
5 to 20
7
15
mn
recl_del
10
Heat Reclaim Deadband
2.7 to 11.1
8
4.4
^F
recl_db
11
Recl Valve Min Position
0 to 50
9
20
%-
min_3w
12
Recl Valve Max Position
20 to 100
10
100
%
max_3w
10
Cir A SCT Ctrl Pt Coef a
1.1 to 11.1
11
4.4
^C
rsp_a_a
11
Cir B SCT Ctrl Pt Coef a
1.1 to 11.1
11
4.4
^C
rsp_a_b
12
Cir A SCT Ctrl Pt Offs b
0 .0to 5.5
12
1.7
^C
rsp_b_a
13
Cir B SCT Ctrl Pt Offs b
0.0 to 5.5
12
1.7
^C
rsp_b_b
14
15
User Password
0 to 150
13
11
-
use_pass
16
Service Password
0 to 150
13
88
-
ser_pass
1.
This decision is only used for the water cooled chillers.
w
0 - no control
w
1 - condenser pump is based on the unit on/off status.
w
2 - condenser pump is ON when unit is ON (compressors are ON )
2.
This decision is only used for the water cooled chillers.
w
1 = water, 2 = medium brine, 3 = low brine
w
If condenser fluid type is brine, condenser pump will not be turned on for condenser freeze protection
function
3.
This decision allows to limit the setpoint of the customer (control point shall be higher than this value). It is
mostly used for brine application, as freezing condition depends on ratio on glycol and water.
4.
Used for cooler heater operation, this item is applied to outside temperature to determine the freeze
conditions (see cooler heater operation section).
5.
This item allows to use capabilities and functions based on CCN and clock..
6.
If enable, when chiller looses communication with the System Manager, it shall force the its CHIL_S_S
variable to «enable» and auto all other variables. Chiller restarts in stand alone mode with default setpoint .
7.
This decision allows to enter the entering temperature dead band for reclaim operation mode. See reclaim
operation description.
8.
This decision allows to enter the delay between two air cooled to reclaim injection sessions. See reclaim
operation description.
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 28 /98
Downloaded from
www.Manualslib.com
manuals search engine