14
Discharge Gas Temp Cp 1
±nnn.n
°F
CPB1_DGT
N
15
Discharge Gas Temp Cp 2
±nnn.n
°F
CPB2_DGT
N
16
Average Discharge Gas Tp
±nnn.n
°F
dt_b
N
17
Motor Temperature Comp 1
±nnn.n
°F
CPB1_TMP
N
18
Motor Temperature Comp 2
±nnn.n
°F
CPB2_TMP
N
19
Motor Current Comp 1
nnn.n
AMPS
CPB1_CUR
N
20
Motor Current Comp 2
nnn.n
AMPS
CPB2_CUR
N
21
EXV Position
0 - 100
%
EXV_B
N
22
Head Press Actuator Pos
0 - 100
%
hd_pos_b
N
23
Cooler Exchange Delta T
n.n
^F
PINCH_B
N
24
Motor Cool TQ in Kohms
nn.n
MTQ_RESB
N
25
Motor Cooling Puls Cycle
nnn
CPB1_PUL
N
DISPLAY SCREEN
TABLE NAME: CIRCB_D PIC TABLE TYPE : 11H, instance 5
DESCRIPTION
STATUS
UNITS
POINTS
FORCEABLE
1
CIRCUIT B DISCRETE
2
3
Compressor 1 Output
On/Off
-
CP_B1
N
4
Cp1 Mtr Cool Solenoid 1
On/Off
-
cpb1_mc1
N
5
Cp1 Mtr Cool Solenoid 2
On/Off
-
cpb1_mc2
N
6
Cp1, Oil Solenoid Out
On/Off
-
cpb1_ols
N
7
Compressor 2 Output
On/Off
-
CP_B2
N
8
Cp2 Mtr Cool Solenoid 1
On/Off
-
cpb2_mc1
N
9
Cp2 Mtr Cool Solenoid 2
On/Off
-
cpb2_mc2
N
10
Cp2, Oil Solenoid Out
On/Off
-
cpb2_ols
N
11
Cir B, Loader 1 Output
On/Off
-
ldr_1_b
N
12
Cir B, Loader 2 Output
On/Off
-
ldr_2_b
N
13
Cir B, Oil Heater Output
On/Off
-
oil_h_b
N
14
Cir B, Oil Level Input
Low/High
-
oil_l_b
N
15
Cir B, Oil Pump Output
On/Off
-
oilpmp_b
N
16
Cir B Refrig Isolate Out
On/Off
-
refb_iso
N
17
18
FANS OUTPUT
19
Fan Output DO # 1
On/Off
-
fan_b1
N
20
Fan Output DO # 2
On/Off
-
fan_b2
N
21
Fan Output DO # 3
On/Off
-
fan_b3
N
22
Fan Output DO # 4
On/Off
-
fan_b4
N
23
Fan Output DO # 5
On/Off
-
fan_b5
N
24
Fan Output DO # 6
On/Off
-
fan_b6
N
25
Fan Output DO # 7
On/Off
-
fan_b7
N
26
Fan Output DO # 8
On/Off
-
fan_b8
N
27
Fan Staging Number
0 - 8
-
FAN_ST_B
N