4.2.5 - User configuration
This configuration is accessible by the customer. Parameters can be modified either through the unit main
interface (see iom manual), the Network Service Tool (see appendix).
4.2.6 - Network configuration
4.2.6.1 - General
This configuration is used to set network functions. It can be done through the Building Supervisor or the Network
Service Tool.
Two network configurations can be implemented on Pro-Dialog control:
w
Setting controller time and date
w
Configuring alarm configuration table
w
Configuring the master/slave function
4.2.6.2 - Configuring a control as a broadcast acknowledger
In order for CCN functions to operate properly,
one and only
one Broadcast Acknowledger is required per bus.
w
Verify that
no other controller on the bus is configured as a broadcast acknowledger
.
w
To configure an element as a Broadcast Acknowledger:
ˆ
Use function (8) of the NETWORK SERVICE TOOL: Address Search
ˆ
Establish connection with the module chosen to be the Broadcast Acknowledger.
ˆ
Position the cursor on driver type and Enter 3.
ˆ
Press F2 to transmit the configuration. This element is now the bus broadcast aknowledger
4.2.6.3 - Setting time and date
The modification of the time and date of a Pro-dialog controller can be done through the network. Setting the
correct date and time is necessary for units connected on a network which collects alarms.
Two methods are available:
w
Through the Network Service Tool in Carrier Control:
ˆ
Select Building-Time. This allows to send time of day, date, day of week to
all
controllers
connected to the network.
ˆ
When Building-Time is selected, the Service Tool clock is displayed:
ˆ
Press F2 to transmit this data to the network. If the displayed time is incorrect, modify your PC
time or set the correct time and date on screen.
Note: If no broadcast aknowledger has been configured on the bus, a communication error will be
displayed. However, controller connected on the network will be set to the date displayed on
screen.
w
Through the Network Service Tool in Carrier Control/Select:
ˆ
Use the Select function to select a controller.
ˆ
Once selected choose Ctrl-Time function
ˆ
Controller-time allows you to view and set the clock functions in the selected device. The clock of
the selected device is read and displayed as shown in the following screen:
ˆ
Type over any incorrect data and press F2 to send the information to the controller.
©