CDE360 Vector Control AC Drive Chapter 7 Fault Detection and Diagnostics
Display
Fault Name
Possible Causes
Solutions
Er/AL38
Accumulative
power-on
time reached
The accumulative power-on time
reaches the setting value.
Clear the record through
the parameter initialization
function.
Er/AL39
Accumulative
running time
reached
The accumulative running time
reaches the setting value.
Clear the record through
the parameter initialization
function.
Er40
Motor
switchover
during
running
status
Change the selection of the motor
via terminal during running of the
drive.
Perform motor switchover after
the drive stops.
Er/AL41
Too large
speed
deviation
The encoder parameters are set
incorrectly.
Set the encoder parameters
properly.
The motor auto-tuning is not
performed.
Perform the motor auto-tuning.
The motor over speed check
parameters are set incorrectly.
Set the motor over speed check
parameters correctly based on
the actual situation.
Er/AL42
Motor over
speed
The encoder parameters are set
incorrectly.
Set the encoder
parameters properly.
The motor auto-tuning is not
performed.
Perform the motor auto-tuning.
The motor over speed check
parameters are set incorrectly.
Set the motor over speed check
parameters correctly based on
the actual situation.
Er/AL43
Flux pole
detection
fault
The encoder signal is incorrectly.
Check encoder status.
Er/AL44
UVW signal
feedback
fault
The encoder signal is incorrectly.
Check encoder status.
Er/AL45
Encoder fault
The encoder type is incorrect.
Set the encoder type correctly
based on the actual situation.
The cable connection of the
encoder is incorrect.
Eliminate external faults.
The encoder is damaged.
Replace the damaged encoder.
The PG card is abnormal.
Replace the abnormal PG card.