CDE360 Vector Control AC Drive Chapter 6 Parameters Description
E5.36
Wake up level
Range: 0.0~200.0
Default: 0.0
Unit/Range depends on
E5.44
.When in sleep mode,if the feedback is
smaller than the value
E5.36
set,and the lasting time exceeds
E5.37
,the
AC drive will quit sleep mode.
E5.37
Range: 0.0~6500.0
Default: 0.0
Wake up delay
time
Unit: Sec
See the description of
E5.36
.
E5.38
Range: 0~1
Default: 0
Sleep mode
0: Base on output frequency
The AC drive enters sleep mode when PID output frequency is
smaller than
E5.40
and the lasting time exceeds
E5.41
.
1: Base on PID feedback
The AC drive enters sleep mode when PID feedback is higher than
E5.39
and the lasting time exceeds
E5.41
.
E5.39
Sleep level
Range: 0.0~200.0
Default: 0.0
Unit/Range depends on
E5.44
.See the description of
E5.38
and the
following figure.
E5.40
Range: 0.00~
b0.00
Default: 0.00
Sleep frequency
Unit: Hz
See the description of
E5.38
and the following figure.
E5.41
Range: 0.0~6500.0
Default: 0.0
Sleep delay
time
Unit: Sec
0 means no sleep function.See the description of
E5.38
and the following
figure.
Here are two examples for two different PID sleep mode.
Example 1: E5.38 = 1(Base on PID feedback).
E5.36
PID
feedback
Running
Stop
Running
AC drive
operation
status
E5.41
E5.37
E5.39
Figure 6- 40 Sleep base on PID feedback