CDE360 Vector Control AC Drive Chapter 6 Parameters Description
C0.18
Range: 0~2
Default: 0
UP/DOWN
Regulation
chose
0: Frequency reference
When b2.00(Frequency source A selection) or b2.02(Auxiliary
frequency source B selection) is set to 0(digital setting b2.01 +
UP/DOWN set), terminal UP/DOWN and keypad regulation will be
superposed to b2.01, the superposition of the results will be the given
of main frequency source A or auxiliary frequency source B.
1: Torque reference
2: PID reference
When E5.04(PID set mode) is set to 0 (digital setting E5.05 +
UP/DOWN), terminal UP/DOWN and keypad regulation will be
superposed to E5.05, the superposition of the results will be used as
PID reference.
C0.19
Range: 00~11
Default: 11
UP/DOWN
adjustment
memory
Units: Retentive at stop
Tens: Retentive at power down
0: No 1: Yes
C0.20
Range: 0.01~100.00
Default: 1.00
Terminal
UP/DOWN ramp
rate
Unit: %
Define terminal UP/DOWN and keypad button regulation change rate.
Larger values change more quickly.
UP/DOWN regulation will be added to the reference setting set by C0.18.
Group C1: Digital Output
C1.00
Range: 0~1
Default: 0
Y2/FO output
choice
0: Pulse output(FO)
1: Switch signal output(Y2)
When set to 0, Y2 terminal act as high speed pulse output(maximum
output frequency is 100KHz), its function is decided by C4.06(FO output
function).
When set to 1, Y2 terminal act as an open collector output, its function is
decided by C1.02.
C1.01
Range: 0~45
Default: 3
Y1 function
The definition of the digital output terminals Y1 function selection, refer to
the table below.