CDE360 Vector Control AC Drive Chapter 6 Parameters Description
d6.17
Range: 0 ~ 60000
Default: 2000
Motor 2
Proportional gain of
flux current loop
Proportional gain of flux current loop.
d6.18
Range: 0 ~ 60000
Default: 800
Motor 2 Integration
time of flux current
loop
Integration time of flux current loop.
d6.19
Range: 0 ~ 60000
Default: 2000
Motor 2
Proportional gain of
torque current loop
Proportional gain of torque current loop.
d6.20
Range: 0 ~ 60000
Default: 400
Motor 2 Integration
time of torque
current loop
Integration time of torque current loop.
Group E0: JOG
JOG function is useful and convenient for equipment debugging,it can make the AC drive
working at any output frequency temporarily.
E0.00
Range: 0.00~
b0.00
Default: 5.00
JOG frequency
Unit: Hz
E0.01
Range: 0.1~6000.0
Default: 10.0
JOG acceleration
time
Unit: Sec
The time JOG running from 0Hz to
b0.00
(Max frequency).
E0.02
Range: 0.1~6000.0
Default: 10.0
JOG deceleration
time
Unit: Sec
The time JOG running from
b0.00
(Max frequency) to 0Hz.
These parameters are used to define the set frequency and acceleration/deceleration time
of the AC drive when JOG running.
The JOG command can be sent from Keypad,Terminal and Communication.
The startup mode is "Ramp start from startup frequency" (
b1.05
= 0) and the stop mode is
depending
on
E0.03
during
JOG
running.