CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Group Eb: Supervision
Eb.00
①
Range: 0~1
Default: 0
Timing function
0: Inactive 1: Active
If the timing function is active,the AC drive begins to time after received a
start commend.And the Y terminal allocated with function NO.32
”Timing
reached” becomes ON when the timing duration reaches the value set by
Eb.02.
Timing duration source is decided by Eb.01.
The rest of timing duration can be watched by A0.28.
Eb.01
①
Range: 0~3
Default: 0
Timing duration
source
0:
Eb.02
1: AI1 2: AI2 3: AI3
The base value is Eb.02 when choose analog input as timing duration
source.
Eb.02
①
Range: 0.0~6500.0
Default: 0.0
Timing duration
Unit: Min
This is timing duration when
Eb.01
is set to 0.
100% analog input equals to Eb.02 when Eb.01 is set to 1~3.
Eb.03
①
Range: 0.0~6500.0
Default: 0.0
Current running
time reached
Unit: Min
The Y terminal allocated with function No.25 ”Current running time
reached” becomes ON when the AC drive current running time reaches
the value set by Eb.03.
Eb.04
Range: 0~9999
Default: 0
Accumulative
power-on
time(day)
threshold
Unit: Day
This parameter is with the use of Eb.05.
The AC drive accumulative power-on time is made up of Eb.04 and Eb.05.
1) Suppose that
Eb.04
= 128 and
Eb.05
= 12.30,then the total
accumulative power-on time is 128 days 12 hours and 18 minutes.
2) The accumulative power-on time reached function is disabled when
simultaneously setting Eb.04 and Eb.05 to 0.
The Y terminal allocated with function NO.23 ”Accumulative power-on time
reached” becomes ON when accumulative power-on time(
A0.54
+
A0.55
)
reaches the set value(
Eb.04
+
Eb.05
).And the AC drive will act as the
hundred’s digit setting of F0.21.
Eb.05
Range: 0.00~23.99
Default: 0.00
Accumulative power-
on time(hour)
threshold
Unit: h
See the parameter description of Eb.04.