CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Eb.09
Range: 0.00~
b0.00
Default: 50.00
Any frequency
reaching
detection value 1
Unit: Hz
If the output frequency of the AC drive is within the positive and negative
amplitudes of Eb.09, the Y terminal allocated with function No.26
“Frequency 1 reached” becomes ON.See the description of Figure below.
Eb.10
Range: 0.0~100.0
Default: 0.0
Any frequency
reaching
detection
amplitude 1
Unit: %
The base value is
b0.00
(Max frequency).
See the description of Figure below.
Eb.11
Range: 0.00~
b0.00
Default: 50.00
Any frequency
reaching
detection value 2
Unit: Hz
If the output frequency of the AC drive is within the positive and negative
amplitudes of Eb.11, the Y terminal allocated with function No.27
“Frequency 2 reached” becomes ON.See the description of Figure below.
Eb.12
Range: 0.0~100.0
Default: 0.0
Any frequency
reaching
detection
amplitude 2
Unit: %
The base value is
b0.00
(Max frequency).
See the description of Figure below.
输出频率
Hz
时间
t
频率检出宽度
任意到达频率
ON
任意到达频
率检测信号
DO
或继电器
ON
OFF
OFF
OFF
频率检出宽度
Figure 6- 53 Any frequency 1/2 reaching detection function diagram
Eb.13
Range: 0.00~
b0.00
Default: 50.00
Frequency
detection
threshold 1
(FDT1)
Unit: Hz
If the running frequency is higher than the value of Eb.13,the Y terminal
allocated with function No.10 “FDT1 detection output” becomes ON. If the
running frequency is lower than value of
Eb.13
*(1-
Eb.14
), the Y terminal
goes OFF.See the description of Figure below.