Section 8. Operation
326
8.3.4.1 File Attributes
A feature of program files is the file attribute. Table
CR800 File Attributes
(p. 326)
lists available file attributes, their functions, and when attributes are typically
used. For example, a program file sent via the support software
Program Send
command, runs a) immediately ("run now"), and b) when power is cycled on the
CR800 ("run on power-up'). This functionality is invoked because
Program Send
sets two CR800 file attributes on the program file, i.e.,
Run Now
and
Run on
Power-up
. When together,
Run Now
and
Run on Power-up
are tagged as
Run
Always
.
Note
Activation of the run-on-power-up file can be prevented by holding down
the
Del
key on the external keyboard / display while the CR800 is powering up.
Table 75.
CR800 File Attributes
Attribute
Function
Attribute for Programs Sent to CR800 with:
Run Always
(run on power-up +
run now)
Runs now and on
power-up.
a)
Send
(p. 431)
1
b)
File Control
2
with
Run Now
& Run on Power-up
selected.
c) Campbell Scientific mass-storage media (USB:
drive) power-up
3
using commands 1 & 13 (see table
Powerup.ini Commands
(p. 329)
).
Run on Power-up
Runs only on
power-up
a)
File Control
2
with
Run on Power-up
checked.
b) Campbell Scientific mass-storage media (USB:
drive) power-up
3
using command 2 (see table
Powerup.ini Commands
(p. 329)
).
Run Now
Runs only when
file sent to CR800
a)
File Control
2
with
Run Now
checked.
b) Campbell Scientific mass-storage media (USB:
drive) power-up
3
using commands 6 & 14 (see
TABLE. Powerup.ini Commands
(p. 329)
). However,
if Campbell Scientific mass-storage media (USB:
drive) is left in, program loads again from Campbell
Scientific mass-storage media (USB: drive).
1
Support software program
Send
(p. 431)
command. See software Help.
2
Support software
File Control
(p. 431).
See software Help &
Preserving Data at Program Send
(p.
110).
3
Automatic on power-up of CR800 with Campbell Scientific mass-storage media (USB: drive)
and Powerup.ini. See
Power-up
(p. 327).
8.3.4.2 Data Preservation
Associated with file attributes is the option to preserve data in CR800 memory
when a program is sent. This option applies to data table SRAM, and support
software
cache data
(p. 426).
Depending on the application, retention of data files
when a program is downloaded may be desirable. When sending a program to the
CR800 with the support software Send command, data are always deleted before
the program runs. When the program is sent using support software
File Control
Send
(p. 431)
command or
CRBasic Editor
Compile, Save and Send
(p. 428)
options
to preserve (not erase) or not preserve (erase) data are presented. The logic in
table
Data-Preserve Options
(p. 327)
summarizes the disposition of CR800 data
depending on the data preservation option selected.
Summary of Contents for CR850
Page 2: ......
Page 4: ......
Page 6: ......
Page 26: ...Table of Contents 26...
Page 30: ...Section 2 Cautionary Statements 30...
Page 32: ...Section 3 Initial Inspection 32...
Page 35: ...Section 4 Quickstart Tutorial 35 Figure 2 Wiring panel...
Page 55: ...Section 4 Quickstart Tutorial 55 Figure 24 PC200W View data utility...
Page 78: ...Section 5 System Overview 78...
Page 80: ...Section 6 CR800 Specifications 80...
Page 267: ...Section 7 Installation 267 Figure 84 Running average signal attenuation...
Page 268: ...Section 7 Installation 268...
Page 384: ...Section 8 Operation 384 Figure 113 Using the keyboard display...
Page 387: ...Section 8 Operation 387 Figure 116 Real time custom...
Page 388: ...Section 8 Operation 388 8 8 1 3 Final Storage Tables Figure 117 Final storage tables...
Page 389: ...Section 8 Operation 389 8 8 2 Run Stop Program Figure 118 Run Stop Program...
Page 390: ...Section 8 Operation 390 8 8 3 File Display Figure 119 File display...
Page 396: ...Section 8 Operation 396...
Page 402: ...Section 9 Maintenance 402...
Page 450: ...Section 11 Glossary 450...
Page 504: ...Appendix A CRBasic Programming Instructions 504...
Page 526: ...Appendix B Status Table and Settings 526...
Page 530: ...Appendix C Serial Port Pinouts 530...
Page 536: ...Appendix E FP2 Data Format 536...
Page 550: ...Appendix F Other Campbell Scientific Products 550...
Page 565: ......