Section 8. Operation
280
duration. Consequently, noise at 1 / (integer multiples) of the integration duration
is effectively rejected by an analog integrator. table
CRBasic Measurement
Integration Times and Codes
(p. 280)
lists three integration durations available in the
CR800 and associated CRBasic codes. If reversing the differential inputs or
reversing the excitation is specified, there are two separate integrations per
measurement; if both reversals are specified, there are four separate integrations.
Table 54.
CRBasic Measurement Integration Times and Codes
Integration Time (ms)
CRBasic Code
Comments
250 µs
250
Fast integration
16.667 ms
_60Hz
Filters 60-Hz noise
20 ms
_50Hz
Filters 50-Hz noise
8.1.2.7.1 ac Power Line Noise Rejection
Grid or mains power (50 or 60 Hz, 230 or 120 Vac) can induce electrical noise at
integer multiples of 50 or 60 Hz. Small analog voltage signals, such as
thermocouples and pyranometers, are particularly susceptible. CR800 voltage
measurements can be programmed to reject (filter) 50-Hz or 60-Hz related noise.
ac Noise Rejection on Small Signals
The CR800 rejects ac power line noise on all voltage ranges except
mV5000
and
mV2500
by integrating the measurement over exactly one ac cycle before A/D
conversion as illustrated in table
ac Noise Rejection on Small Signals
(p. 280)
and
the full cycle technique of figure
ac Power Line Noise Rejection Techniques
(p.
281).
Table 55.
ac Noise Rejection on Small Signals
Applies to all analog input voltage ranges except
mV2500
and
mV5000
.
ac Power Line Frequency
Measurement Integration
Duration
CRBasic Integration Code
60 Hz
16.667 ms
_60Hz
50 Hz
20 ms
_50Hz
Summary of Contents for CR850
Page 2: ......
Page 4: ......
Page 6: ......
Page 26: ...Table of Contents 26...
Page 30: ...Section 2 Cautionary Statements 30...
Page 32: ...Section 3 Initial Inspection 32...
Page 35: ...Section 4 Quickstart Tutorial 35 Figure 2 Wiring panel...
Page 55: ...Section 4 Quickstart Tutorial 55 Figure 24 PC200W View data utility...
Page 78: ...Section 5 System Overview 78...
Page 80: ...Section 6 CR800 Specifications 80...
Page 267: ...Section 7 Installation 267 Figure 84 Running average signal attenuation...
Page 268: ...Section 7 Installation 268...
Page 384: ...Section 8 Operation 384 Figure 113 Using the keyboard display...
Page 387: ...Section 8 Operation 387 Figure 116 Real time custom...
Page 388: ...Section 8 Operation 388 8 8 1 3 Final Storage Tables Figure 117 Final storage tables...
Page 389: ...Section 8 Operation 389 8 8 2 Run Stop Program Figure 118 Run Stop Program...
Page 390: ...Section 8 Operation 390 8 8 3 File Display Figure 119 File display...
Page 396: ...Section 8 Operation 396...
Page 402: ...Section 9 Maintenance 402...
Page 450: ...Section 11 Glossary 450...
Page 504: ...Appendix A CRBasic Programming Instructions 504...
Page 526: ...Appendix B Status Table and Settings 526...
Page 530: ...Appendix C Serial Port Pinouts 530...
Page 536: ...Appendix E FP2 Data Format 536...
Page 550: ...Appendix F Other Campbell Scientific Products 550...
Page 565: ......