PTP 800 Series User Guide
Grounding and light ning prot ect ion
phn- 2513_004v000 ( Oct 2012)
2- 15
Protection inside the building
Inside multi-story or high rise buildings (
), ensure that the installation meets the
following requirements:
•
The IF cable shield is bonded
to the
building grounding system at the entry point to the
building.
•
The IF cable shield is bonded
to the
building grounding system at the entry point to the
equipment area.
•
An LPU is installed within 600 mm (24 in) of the entry point to the equipment area.
Figu r e 4 6
Gr ounding and light ning prot ect ion inside high building