Consult the table below for recommended wire size by model number and AC input rating.
MODEL
INPUT VOLTAGE
INPUT CURRENT
RECOMMENDED
INPUT SERVICE
MINIMUM COPPER
WIRE SIZE, 75°C RATED
390AFX-2
208 V ac, 3~
37 A rms, max
40 A rms
10 mm^2 (AWG 8)
3120AFX-2
208 V ac, 3~
48 A rms, max
50 A rms
10 mm^2 (AWG 8)
3150AFX-2
208 V ac, 3~
55 A rms, max
60 A rms
16 mm^2 (AWG 6)
390AFX-4
380/400 V ac, 3~
480 V ac, 3~
20 A rms, max
16 A rms, max
25 A rms
20 A rms
6 mm^2 (AWG 10)
4 mm^2 (AWG 12)
3120AFX-4
380/400 V ac, 3~
480 V ac, 3~
27 A rms, max
22 A rms, max
30 A rms
25 A rms
6 mm^2 (AWG 10)
6 mm^2 (AWG 10)
3150AFX-4
380/400 V ac, 3~
480 V ac, 3~
30 A rms, max
24 A rms, max
35 A rms
30 A rms
10 mm^2 (AWG 8)
6 mm^2 (AWG 10)
Table 5-1: AC Input Wire Size Table
The AC input connections must be made at the rear panel AC terminal block. This input
block has a removable safety cover that must be installed when the instruments is used on a
bench or is otherwise accessible at the rear. If mounted in a cabinet with a locked door or
screen, the AC input safety cover may be omitted if needed.
Figure 5-3: Rear Panel Layout
The AC input terminal phasing is marked on the rear panel and shown in the illustration
below. A four wire mains connection is required. (L1, L2, L3 and Earth Ground). Ground
connection is located directly below the AC Line input terminal block as shown in Figure 5-3
above.
EARTH GROUND